Inspections for the day of: Monday, January 3, 2005.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MIS04-00339 FIR-Final12/30/20041/3/20051/3/2005 12:00:00 AMAPASS
lavor ###-####
FIR04-00448 INSP-Sprinkler Rough-in1/3/20051/3/20051/3/2005 12:00:00 AMPFAIL
Contact: Vance - Walt thru - would like around 1:30 PM - please call to confirm; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Flow switch on east riser not operating properly 1/3/2005 2:57:29 PM
BLD04-01762 FIRE-Final Inspection1/3/20051/3/20051/3/2005 12:00:00 AMPPASS
PLease call at least a half hour prior to inspection///george; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Emergency lighting installed per plans; exit door deadbolt releases with lever 1/3/2005 9:19:59 AM
BLD04-01827 FIRE-Final Inspection1/3/20051/3/20051/3/2005 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 1/3/2005 at 10:06:26 AM. Contact: ###-####. Need extinguishers; ceiling required in south janitor and SE mechanical 1/3/2005 4:27:35 PM
FIR04-00767 INSP-Final Inspection1/3/20051/3/20051/3/2005 12:00:00 AMPFAIL
FACP not on dedicated circuit; need updated map; AHU 19 detector cycles on alarm; need record of completion; 1/3/2005 4:26:58 PM
FIR04-00753 INSP-Sprinkler Rough-in12/29/20041/3/20051/3/2005 12:00:00 AMPPART
This is a rough to cover. Our contact is Scott Carter at ###-####; Phone #: ###-#### Internet Inspection Request from: Trent Bice Okay to cover - as-builts needed for changes to piping; riser not complete and will have changes from approved plan 1/3/2005 1:00:40 PM