Inspections for the day of: Monday, January 3, 2005.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD04-02514 FIRE-Final Inspection12/30/20041/3/20051/3/2005 12:00:00 AMAFAIL
Lower pendant head in the data room and provide suite number. Per Linda at Mountain Alarm hvac units are already supervised at roof 1/3/2005 10:23:58 AM
BLD04-02789 FIRE-Final Inspection12/31/20041/3/20051/3/2005 12:00:00 AMAPART
A temporary occupancy was given until the thumbturn is removed from the main exit. 1/3/2005 10:21:50 AM
BLD04-02479 FIRE-Final Inspection1/3/20051/3/20051/3/2005 12:00:00 AMPFAIL
Provide fire extinguisher, Provide compliance with IFC 1003.3.1.3.4 for the access controled egress doors. Provide access to the fire sprinkler riser room for verification on max sprinkler spacing and test the exit signs. 1/3/2005 2:51:13 PM
FIR04-00627 INSP-Sprinkler Rough-in1/3/20051/3/20051/3/2005 12:00:00 AMPPART
Underground supply piping is ok to cover for an additional 160' east of the roadway previously approved for cover 1/3/2005 4:00:03 PM
BLD04-02789 FIRE-Final Inspection1/3/20051/3/20051/3/2005 12:00:00 AMPPASS
Fire life safety finaled