FIR05-00152
| INSP-Supply line flush | 12/30/2005 | 1/3/2006 | 1/3/2006 2:12:54 PM | P | NR |
|
|
UG hydrostatic test not ready as the guage was below 200 psi at the begining of the test.
|
FIR05-00190
| INSP-Sprinkler Rough-in/Hydro | 1/3/2006 | 1/3/2006 | 1/3/2006 2:08:57 PM | P | PART |
|
|
Overhead rough-in at area as marked on approved plan is acceptable, escutcheons at hard lid ceilings are missing, a 2" threaded tee is leaking- location marked on plans.
|
BLD05-03044
| FIRE-Conference | 1/3/2006 | 1/3/2006 | 1/3/2006 11:42:11 AM | P | DONE |
|
|
Discussion regarding fire sprinkler riser modification requirements.
|
BLD05-03075
| FIRE-Final Inspection | 12/30/2005 | 1/3/2006 | 1/3/2006 12:00:00 AM | P | CANC |
|
|
jerry ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie///cancelled per Jerry 1/3/06 12 :14 pm LEG
|