FIR10-00529
| FIR-Aging Inspection | 1/3/2011 | 1/3/2011 | 1/10/2011 9:24:09 AM | | NR |
|
|
Per charlie this will be called in within the next couple of weeks with building 5
|
FIR10-00028
| FIR-Aging Inspection | 1/3/2011 | 1/3/2011 | 1/10/2011 9:12:04 AM | | NR |
|
|
work is in progress
|
BLD10-02793
| FIRE-Final Inspection | 1/3/2011 | 1/3/2011 | 1/4/2011 2:29:04 PM | P | FAIL |
|
|
In one location sprinkler pendants are located too close and in another area they are 18' apart. Per the building plans part of this space is being used as "Library Stack". Most of the pendants are spaced less than 130 sq. ft. but the concern is what is the design density. Other life safety items are ok.
|
FIR10-00445
| INSP-Final Inspection | 1/2/2011 | 1/3/2011 | 1/3/2011 3:07:35 PM | A | CANC |
|
|
not ready for final inspection
|
FIR09-00530
| INSP-Final Inspection | 12/30/2010 | 1/3/2011 | 1/3/2011 3:02:14 PM | P | PASS |
|
|
Permit finaled.The netcon was a 5.
|
FIR09-00111
| INSP-Final Inspection | 12/30/2010 | 1/3/2011 | 1/3/2011 2:57:09 PM | P | FAIL |
|
|
Provide a map at the facp and repair the outside electric alarm bell.
|
FIR09-00107
| INSP-Final Inspection | 12/30/2010 | 1/3/2011 | 1/3/2011 1:32:49 PM | A | FAIL |
|
|
To final this permit both flow switches and both PIV tamper switches need to be tested. The inspector test lines do not have the required orfice mounted therefore a test or these devices could not be completed.
|
BLD10-00851
| FIRE-Final Inspection | 12/30/2010 | 1/3/2011 | 1/3/2011 1:26:10 PM | A | FAIL |
|
|
Mount the fire extinguisher as discussed. Per Tim a resubmittal would not be required for the counter as long as it met code.
|
FIR10-00615
| INSP-Final Inspection | 12/30/2010 | 1/3/2011 | 1/3/2011 11:17:36 AM | A | PASS |
|
|
Permit finaled
|
FIR10-00635
| INSP-Sprinkler Rough-in | 1/2/2011 | 1/3/2011 | 1/3/2011 10:42:41 AM | A | PASS |
|
|
The sprinkler piping located above the ceilings can be covered. See the city approved plans for upright heads at two locations in the warehouse that are located too close to one another.
|