FIR16-00510
| INSP-Sprinkler Rough-in | 1/3/2017 | 1/3/2017 | 1/3/2017 2:52:00 PM | P | PASS |
|
|
Tenting inspection for level 3 fire sprinkler piping in attic spaces complete, approved for cover.
|
FIR15-00900
| INSP-Supply line flush | 1/3/2017 | 1/3/2017 | 1/3/2017 2:51:08 PM | P | CANC |
|
|
Piping installed between underground to backflow was not the correct size, piping installed is 1 1/4 piping and the approved drawings shows an 1 1/2 supply, pipe replacement for correct size will be verified at final inspection.
|
FIR16-00223
| INSP-Sprinkler Rough-in | 1/3/2017 | 1/3/2017 | 1/3/2017 2:47:56 PM | P | PART |
|
|
Rough in inspection complete for overhead fire sprinkler piping below mezzanine on level one and basement level dry system.
|
FIR16-00101
| INSP-Sprinkler Rough-in | 1/3/2017 | 1/3/2017 | 1/3/2017 12:52:26 PM | P | PART |
|
|
Rough to cover inspection for sprinkler piping/sprinklers located in level 2 room entries complete, approved for cover.
|
FIR16-00609
| INSP-Final Inspection | 1/2/2017 | 1/3/2017 | 1/3/2017 9:50:30 AM | A | PASS |
|
|
Final fire alarm inspection for area of work passed/complete
|
FIR16-00736
| INSP-Final Inspection | 1/2/2017 | 1/3/2017 | 1/3/2017 9:50:08 AM | A | PASS |
|
|
Final fire alarm inspection for area of work passed/complete
|
FIR16-00469
| INSP-Final Inspection | 1/2/2017 | 1/3/2017 | 1/3/2017 9:49:30 AM | A | PASS |
|
|
Final fire alarm inspection for area of work passed/complete
|