Inspections for the day of: Tuesday, January 3, 2017.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00510 INSP-Sprinkler Rough-in1/3/20171/3/20171/3/2017 2:52:00 PMPPASS
Tenting inspection for level 3 fire sprinkler piping in attic spaces complete, approved for cover.
FIR15-00900 INSP-Supply line flush1/3/20171/3/20171/3/2017 2:51:08 PMPCANC
Piping installed between underground to backflow was not the correct size, piping installed is 1 1/4 piping and the approved drawings shows an 1 1/2 supply, pipe replacement for correct size will be verified at final inspection.
FIR16-00223 INSP-Sprinkler Rough-in1/3/20171/3/20171/3/2017 2:47:56 PMPPART
Rough in inspection complete for overhead fire sprinkler piping below mezzanine on level one and basement level dry system.
FIR16-00101 INSP-Sprinkler Rough-in1/3/20171/3/20171/3/2017 12:52:26 PMPPART
Rough to cover inspection for sprinkler piping/sprinklers located in level 2 room entries complete, approved for cover.
FIR16-00609 INSP-Final Inspection1/2/20171/3/20171/3/2017 9:50:30 AMAPASS
Final fire alarm inspection for area of work passed/complete
FIR16-00736 INSP-Final Inspection1/2/20171/3/20171/3/2017 9:50:08 AMAPASS
Final fire alarm inspection for area of work passed/complete
FIR16-00469 INSP-Final Inspection1/2/20171/3/20171/3/2017 9:49:30 AMAPASS
Final fire alarm inspection for area of work passed/complete