Inspections for the day of: Thursday, January 3, 2019.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-03523 Final12/28/20181/3/20191/3/2019 2:03:40 PMPFAIL
Phone #: ###-#### Inspection requested via web by steve ragan
See rough in
ELE18-03523 Electrical Rough-In1/3/20191/3/20191/3/2019 1:06:04 PMPFAIL
Phone #: ###-#### Inspection requested via web by steve ragan
334.12(B)(2)- NM cable shall not be installed in a wet location.
550.15(H)- Under chassis wiring is exposed and shall be protected from physical damage, and shall be identified for wet locations.
ELE19-00033 Temporary Service1/2/20191/3/20191/3/2019 10:27:27 AMAFAIL
Temp pole Phone #: ###-#### Inspection requested via web by cal crosby
110.12(B)- Internal parts shall be free of foreign materials. Remove dirt, leaves, and cob webs.
590.6(B)- Temp power receptacles other than 120 volt shall have GFCI protection. Standard 240 installed on 50 amp receptacle.
ELE19-00032 Permanent Service1/2/20191/3/20191/3/2019 9:48:22 AMACANC
Temp pole Phone #: ###-#### Inspection requested via web by cal crosby
Needed temp service inspection
ELE19-00032 Temporary Service1/3/20191/3/20191/3/2019 9:48:10 AMPPASS
Temp pole Phone #: ###-#### Inspection requested via web by cal crosby
t/s u/g n ok
ELE19-00035 Final1/2/20191/3/20191/3/2019 9:11:49 AMAPASS
Phone #: ###-#### Inspection requested via web by steve ragan Final ok
ELE19-00035 Electrical Rough-In1/3/20191/3/20191/3/2019 9:11:34 AMPPASS
Phone #: ###-#### Inspection requested via web by steve ragan
Change diffusers and install square surface mount luminaires rough in ok