ELE18-03523
| Final | 12/28/2018 | 1/3/2019 | 1/3/2019 2:03:40 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by steve ragan See rough in
|
ELE18-03523
| Electrical Rough-In | 1/3/2019 | 1/3/2019 | 1/3/2019 1:06:04 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by steve ragan 334.12(B)(2)- NM cable shall not be installed in a wet location. 550.15(H)- Under chassis wiring is exposed and shall be protected from physical damage, and shall be identified for wet locations.
|
ELE19-00033
| Temporary Service | 1/2/2019 | 1/3/2019 | 1/3/2019 10:27:27 AM | A | FAIL |
|
|
Temp pole Phone #: ###-#### Inspection requested via web by cal crosby 110.12(B)- Internal parts shall be free of foreign materials. Remove dirt, leaves, and cob webs. 590.6(B)- Temp power receptacles other than 120 volt shall have GFCI protection. Standard 240 installed on 50 amp receptacle.
|
ELE19-00032
| Permanent Service | 1/2/2019 | 1/3/2019 | 1/3/2019 9:48:22 AM | A | CANC |
|
|
Temp pole Phone #: ###-#### Inspection requested via web by cal crosby Needed temp service inspection
|
ELE19-00032
| Temporary Service | 1/3/2019 | 1/3/2019 | 1/3/2019 9:48:10 AM | P | PASS |
|
|
Temp pole Phone #: ###-#### Inspection requested via web by cal crosby t/s u/g n ok
|
ELE19-00035
| Final | 1/2/2019 | 1/3/2019 | 1/3/2019 9:11:49 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by steve ragan Final ok
|
ELE19-00035
| Electrical Rough-In | 1/3/2019 | 1/3/2019 | 1/3/2019 9:11:34 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by steve ragan Change diffusers and install square surface mount luminaires rough in ok
|