Inspections for the day of: Thursday, January 30, 2003.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE02-01011 ELE-Aging Inspection1/30/20031/30/20031/30/2003 12:00:00 AM PART
WSUC 1/30/2003 7:34:26 AM
ELE02-01013 ELE-Aging Inspection1/30/20031/30/20031/30/2003 12:00:00 AM PART
WSUC 1/30/2003 7:34:40 AM
ELE03-00246 Electrical Rough-In1/30/20031/30/20031/30/2003 12:00:00 AMAFAIL
cor. posted called 314.3 needs bond bushings for metal raceways non metallic box 250.146,148 grd all switches and aecepts raised covers
ELE03-00246 Permanent Service1/30/20031/30/20031/30/2003 12:00:00 AMAPASS
p/s o/h rec. ok
ELE03-00246 Final1/29/20031/30/20031/30/2003 12:00:00 AMAFAIL
###-#### no power see added r/i ,p/s 1/30/2003 9:47:25 AM
ELE02-02685 Electrical Rough-In1/29/20031/30/20031/30/2003 12:00:00 AMAPART
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung ceilings west phase ok 1/30/2003 9:22:09 AM
ELE02-03870 Final1/29/20031/30/20031/30/2003 12:00:00 AMANH
jimmy--call 1st before insp; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called could not provide access Jimmy will reschedule 1/30/2003 8:29:59 AM
ELE02-03697 Final1/29/20031/30/20031/30/2003 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 01/29/2003 at 15:00:55. Contact: ###-####. ok card signed 1/30/2003 12:38:39 PM
ELE03-00154 Rough-In Permanent Service1/29/20031/30/20031/30/2003 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 01/29/2003 at 17:12:03. Contact: ###-####. cor. posted met owner 300.10 shall use locknuts inside, outside for p/s and meter base needs 4 locknuts only has 2 1/30/2003 12:02:52 PM
ELE02-02264 Electrical Rough-In1/30/20031/30/20031/30/2003 12:00:00 AMAPART
###-#### 1st floor next to elev. north side ok 1/31/2003 8:27:21 AM
ELE03-00228 Permanent Service1/27/20031/30/20031/30/2003 12:00:00 AMPNH
###-#### kevin notice posted called 1/30/2003 4:41:15 PM
ELE03-00253 Final1/29/20031/30/20031/30/2003 12:00:00 AMPFAIL
for homeowner ###-####- tim--call 1st before insp -or kevin at ###-#### if any problems cor. posted 210.52 (B)(3) serve counters with 2 circuits, 314.43 no screws allowed in plastic boxes, 225.38 disconnect for garage, 334.15 protect romex in unfinished garage 1/30/2003 2:05:18 PM
ELE03-00261 Electrical Rough-In1/30/20031/30/20031/30/2003 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 01/30/2003 at 10:44:54. Contact: ###-####. office walls and restrooms 1/30/2003 3:27:50 PM
ELE02-03524 Final1/30/20031/30/20031/30/2003 12:00:00 AMPPASS
sign corrections made ok card signed 1/30/2003 12:40:32 PM
ELE02-03262 Final1/30/20031/30/20031/30/2003 12:00:00 AMPCANC
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung contractor called 1/30/2003 3:06:54 PM
ELE03-00067 Final1/30/20031/30/20031/30/2003 12:00:00 AMPNR
Scheduled by a contractor via Hello! on 01/30/2003 at 09:41:16. Contact: ###-####. conference ok 1/30/2003 4:28:43 PM
ELE02-03697 Electrical Rough-In1/29/20031/30/20031/29/2003 12:00:00 AMACANC
Scheduled by a contractor via Hello! on 1/29/2003 at 2:52:22 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on 01/29/2003 at 14:59:41.