Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE03-01999 Final1/26/20041/30/20041/30/2004 12:00:00 AMAPASS
WE ARE LOOKING FOR A FINAL ON THIS PROJECT AND THE HOMEOWNER WILL BE THERE TO LET YOU IN. HOME OWNER NAME IS RAY HOOD. THANK YOU; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH ok 1/30/2004 8:44:23 AM
ELE04-00146 Rough-In Permanent Service1/29/20041/30/20041/30/2004 12:00:00 AMAFAIL
Joe; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes cor. posted called 314.16 box fill everywhere, 300.4 nail plates and 11/4" 422.15 and 210.23(A) needs #12 for vacuum outlet on 20 amp circuits and vacuum outlets not allowed on kit. circuit, replace damaged 12/2 romex stairs landing garage wall 1/30/2004 11:31:47 AM
ELE04-00161 Permanent Service1/29/20041/30/20041/30/2004 12:00:00 AMAPASS
dan ###-#### p/s o/h rec. ok 1/30/2004 10:16:08 AM
ELE04-00241 Electrical Rough-In1/29/20041/30/20041/30/2004 12:00:00 AMAPART
j-kel ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie walls for computer trainer center 1/30/2004 9:15:14 AM
ELE04-00007 Final1/29/20041/30/20041/30/2004 12:00:00 AMAPASS
bob; Phone #: ###-#### Internet Inspection Request from: Annette Moore ok 1/30/2004 9:54:20 AM
ELE04-00260 Conference1/29/20041/30/20041/30/2004 12:00:00 AMAPART
###-#### brian ok 1/30/2004 11:49:17 AM
ELE04-00234 Temporary Service1/29/20041/30/20041/30/2004 12:00:00 AMAPASS
Phone #: ###-#### Internet Inspection Request from: William Zerfas
t/s o/h new ok 1/30/2004 8:05:37 AM
ELE04-00269 Permanent Service1/30/20041/30/20041/30/2004 12:00:00 AMPPASS
dave ; Phone #: ###-#### Internet Inspection Request from: Annette Moore
p/s o/h rec. ok 1/30/2004 3:03:09 PM
ELE04-00227 Electrical Rough-In1/30/20041/30/20041/30/2004 12:00:00 AMPPASS
andy ; Phone #: ###-#### Internet Inspection Request from: Annette Moore new back of house ok 1/30/2004 12:47:20 PM
ELE04-00280 Temporary Service1/30/20041/30/20041/30/2004 12:00:00 AMPPASS
###-#### mike
t/s u/g new ok 1/30/2004 1:25:53 PM
ELE04-00110 Final1/30/20041/30/20041/30/2004 12:00:00 AMPPASS
we are relocating existing bathroom switches and gfci receptacle. we are alo adding a fan/lt in the bathroom. In the kitchen we are replacing existing outlets with gfci receptacles.; Phone #: ###-#### Internet Inspection Request from: Joe Thomas ok 1/30/2004 2:04:58 PM
ELE03-00160 Final1/30/20041/30/20041/30/2004 12:00:00 AMPCANC
ELE04-00160 Final1/30/20041/30/20041/30/2004 12:00:00 AMPPASS
ok correction made 1/30/2004 3:27:39 PM