Inspections for the day of: Monday, January 30, 2006.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-04154 Final1/30/20061/30/20061/30/2006 3:43:42 PMPPASS
ready for final inspection. water heater conected and conduit exposed to shed. thank you.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH ok called needs switch for shed
ELE05-04175 ELE-Aging Inspection1/30/20061/30/20061/30/2006 3:17:21 PM PART
wsuc
ELE06-00329 Electrical Rough-In1/29/20061/30/20061/30/2006 3:02:57 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: joe wheeler
cor do not cover posted called, BCC 04.05.31 part (D) all wiring shall be raceway for comm. wiring note sign circuit required also
ELE05-04666 Electrical Rough-In1/30/20061/30/20061/30/2006 2:24:56 PMPNR
ceiling insp hp; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
electrical ok cor. posted for low voltage,
800.21,24, 300.11 shal support L V cables as codes noted states
ELE05-04666 Electrical Rough-In1/30/20061/30/20061/30/2006 2:22:31 PMPCANC
Scheduled by a contractor via Hello! on 1/30/2006 at 7:56:20 AM. Contact: ###-####.
ELE06-00125 Electrical Rough-In1/30/20061/30/20061/30/2006 1:43:16 PMPPART
This is for underground inspection only. Call Ryan with any questions at 573.1871; Phone #: ###-#### Internet Inspection Request from: Daniel Gamboa all u/g in building slab ok no outside
ELE05-04134 ELE-Aging Inspection1/30/20061/30/20061/30/2006 1:11:21 PM PASS
ELE05-04497 Electrical Rough-In1/27/20061/30/20061/30/2006 12:35:36 PMPNR
Kathy -- for temporary occupancy; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong this permit is for shell and tenant space combined needs new ele permit for bld 05-01860 tenant space
ELE06-00214 Electrical Rough-In1/30/20061/30/20061/30/2006 11:53:25 AMPPART
ufer ground inspection//casey ###-#### ok for dirt cover
ELE06-00322 Electrical Rough-In1/27/20061/30/20061/30/2006 10:13:56 AMAPART
###-#### - cathy Note: uifer and trench for conduit ok dirt cover
ELE06-00199 Rough-In Permanent Service1/27/20061/30/20061/30/2006 10:13:00 AMAPASS
i need permanent service inspection. the meter pak is on the back of the bld. the back of the bld. is facing overland. if you could at least sign the inspection tag or leave a sticker the general contractor would greatly appeciate you doing this; Phone #: ###-#### Internet Inspection Request from: joe wheeler no r/i p/s u/g new ok
ELE05-03384 Rough-In Permanent Service1/30/20061/30/20061/30/2006 9:42:16 AMAFAIL
inspection for detached garage Internet Inspection Request from: Shaun Kirkman
cor. met contractor 314.20 outside boxes shall be flush with siding, complete makeup also, )(3), 52(D) outlet and bathrm circut, 250.32 needs GEC to rebar update permit for p/s on garage
ELE06-00252 Rough-In Permanent Service1/27/20061/30/20061/30/2006 9:03:36 AMAFAIL
210.52(B) remove vacuum outlet from kit. cuitcuit in din rm cor. called
ELE05-04118 Permanent Service1/29/20061/30/20061/30/2006 8:22:48 AMANR
Scheduled by a contractor via Hello! on 1/29/2006 at 3:30:18 PM. Contact: ###-####. called
ELE05-04134 Final1/30/20061/30/20061/30/2006 12:00:00 AMPPASS
ok