ELE05-04154
| Final | 1/30/2006 | 1/30/2006 | 1/30/2006 3:43:42 PM | P | PASS |
|
|
ready for final inspection. water heater conected and conduit exposed to shed. thank you.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH ok called needs switch for shed
|
ELE05-04175
| ELE-Aging Inspection | 1/30/2006 | 1/30/2006 | 1/30/2006 3:17:21 PM | | PART |
|
|
wsuc
|
ELE06-00329
| Electrical Rough-In | 1/29/2006 | 1/30/2006 | 1/30/2006 3:02:57 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: joe wheeler cor do not cover posted called, BCC 04.05.31 part (D) all wiring shall be raceway for comm. wiring note sign circuit required also
|
ELE05-04666
| Electrical Rough-In | 1/30/2006 | 1/30/2006 | 1/30/2006 2:24:56 PM | P | NR |
|
|
ceiling insp hp; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie electrical ok cor. posted for low voltage, 800.21,24, 300.11 shal support L V cables as codes noted states
|
ELE05-04666
| Electrical Rough-In | 1/30/2006 | 1/30/2006 | 1/30/2006 2:22:31 PM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 1/30/2006 at 7:56:20 AM. Contact: ###-####.
|
ELE06-00125
| Electrical Rough-In | 1/30/2006 | 1/30/2006 | 1/30/2006 1:43:16 PM | P | PART |
|
|
This is for underground inspection only. Call Ryan with any questions at 573.1871; Phone #: ###-#### Internet Inspection Request from: Daniel Gamboa all u/g in building slab ok no outside
|
ELE05-04134
| ELE-Aging Inspection | 1/30/2006 | 1/30/2006 | 1/30/2006 1:11:21 PM | | PASS |
|
|
|
ELE05-04497
| Electrical Rough-In | 1/27/2006 | 1/30/2006 | 1/30/2006 12:35:36 PM | P | NR |
|
|
Kathy -- for temporary occupancy; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong this permit is for shell and tenant space combined needs new ele permit for bld 05-01860 tenant space
|
ELE06-00214
| Electrical Rough-In | 1/30/2006 | 1/30/2006 | 1/30/2006 11:53:25 AM | P | PART |
|
|
ufer ground inspection//casey ###-#### ok for dirt cover
|
ELE06-00322
| Electrical Rough-In | 1/27/2006 | 1/30/2006 | 1/30/2006 10:13:56 AM | A | PART |
|
|
###-#### - cathy Note: uifer and trench for conduit ok dirt cover
|
ELE06-00199
| Rough-In Permanent Service | 1/27/2006 | 1/30/2006 | 1/30/2006 10:13:00 AM | A | PASS |
|
|
i need permanent service inspection. the meter pak is on the back of the bld. the back of the bld. is facing overland. if you could at least sign the inspection tag or leave a sticker the general contractor would greatly appeciate you doing this; Phone #: ###-#### Internet Inspection Request from: joe wheeler no r/i p/s u/g new ok
|
ELE05-03384
| Rough-In Permanent Service | 1/30/2006 | 1/30/2006 | 1/30/2006 9:42:16 AM | A | FAIL |
|
|
inspection for detached garage Internet Inspection Request from: Shaun Kirkman cor. met contractor 314.20 outside boxes shall be flush with siding, complete makeup also, )(3), 52(D) outlet and bathrm circut, 250.32 needs GEC to rebar update permit for p/s on garage
|
ELE06-00252
| Rough-In Permanent Service | 1/27/2006 | 1/30/2006 | 1/30/2006 9:03:36 AM | A | FAIL |
|
|
210.52(B) remove vacuum outlet from kit. cuitcuit in din rm cor. called
|
ELE05-04118
| Permanent Service | 1/29/2006 | 1/30/2006 | 1/30/2006 8:22:48 AM | A | NR |
|
|
Scheduled by a contractor via Hello! on 1/29/2006 at 3:30:18 PM. Contact: ###-####. called
|
ELE05-04134
| Final | 1/30/2006 | 1/30/2006 | 1/30/2006 12:00:00 AM | P | PASS |
|
|
ok
|