Inspections for the day of: Monday, January 30, 2006.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-04564 Final1/30/20061/30/20061/30/2006 4:14:18 PMPPASS
mike ###-#### ok to final
ELE05-04062 Final1/30/20061/30/20061/30/2006 4:04:20 PMPPASS
chad ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok to final
ELE05-03763 ELE-Aging Inspection1/30/20061/30/20061/30/2006 3:51:41 PM DONE
see final
ELE05-03761 ELE-Aging Inspection1/30/20061/30/20061/30/2006 3:50:32 PM DONE
see final
ELE05-02060 Final1/30/20061/30/20061/30/2006 2:58:51 PMPPASS
John; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong talked to contr, ok to final at this time, further work will need a new permit
ELE06-00303 Final1/30/20061/30/20061/30/2006 2:57:20 PMPPASS
corrections requested by Bob Reichart performed; Phone #: ###-#### Internet Inspection Request from: Celinda Winters p/s o/h reconnected, ok to final
ELE06-00301 Permanent Service1/30/20061/30/20061/30/2006 2:35:36 PMPCANC
james; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa they need a permit for the core and shell, and breakers before calling for power.
ELE06-00324 Electrical Rough-In1/27/20061/30/20061/30/2006 1:59:59 PMPPASS
rough in inspection; Phone #: ###-#### Internet Inspection Request from: Tyler Bowen ric ok.
ELE06-00331 Rough-In Permanent Service1/30/20061/30/20061/30/2006 12:58:19 PMPPASS
paul ###-#### ric ok, p/s u/g n ok
ELE06-00281 Electrical Rough-In1/30/20061/30/20061/30/2006 10:08:23 AMPPASS
Brian; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong walls ok to cover
ELE06-00319 Electrical Rough-In1/27/20061/30/20061/30/2006 10:05:14 AMAPASS
UFFER GROUND INSPECTION; Phone #: ###-#### Internet Inspection Request from: JENNY EMEL called contr, ok to pour gec
ELE06-00301 Electrical Rough-In1/27/20061/30/20061/30/2006 9:21:22 AMAPASS
Scheduled by a contractor via Hello! on 1/27/2006 at 12:16:10 PM. Contact: ###-####. walls only ok to cover
ELE06-00303 Final1/27/20061/30/20061/30/2006 8:37:04 AMAFAIL
brandon; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa see ps
ELE06-00303 Permanent Service1/27/20061/30/20061/30/2006 8:35:46 AMAFAIL
brandon; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called contr, left corr notice, 250.56 A single electrode shall be augmented by 1 additional electrode, 6' apart., 408.4 circuit directory shall be provided, 210.52(A)(1) shall use metal water pipe within 5' of bldg as grounding electrode
ELE06-00244 Electrical Rough-In1/30/20061/30/20061/30/2006 12:00:00 AMPPASS
u/g ok, under driveway to gate operator
ELE04-02771 Final1/30/20061/30/20061/30/2006 12:00:00 AMPPASS
looked at sign, ok to final
ELE05-03761 Final1/30/20061/30/20061/30/2006 12:00:00 AMPPASS
looked at signs, ok to final
ELE05-03763 Final1/30/20061/30/20061/30/2006 12:00:00 AMPPASS
looked at signs, ok to final