ELE06-00482
| Conference | 1/30/2007 | 1/30/2007 | 1/30/2007 3:09:52 PM | P | DONE |
|
|
stopped at job site wsuc
|
ELE06-03996
| Final | 1/29/2007 | 1/30/2007 | 1/30/2007 2:46:50 PM | P | NH |
|
|
if locked please call for access code at- ###-#### thanks Phone #: ###-#### called no access to front unit code would not work back unit ok both units need panel directory to be specific to location purpose and use 408.4
|
ELE06-01186
| Electrical Rough-In | 1/30/2007 | 1/30/2007 | 1/30/2007 2:21:46 PM | P | PASS |
|
|
elijah; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles r/i ok
|
ELE07-00278
| Final | 1/30/2007 | 1/30/2007 | 1/30/2007 1:57:42 PM | P | PASS |
|
|
paul; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles final ok
|
ELE07-00278
| Electrical Rough-In | 1/30/2007 | 1/30/2007 | 1/30/2007 1:57:20 PM | P | PASS |
|
|
paul; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
|
ELE07-00326
| Electrical Rough-In | 1/30/2007 | 1/30/2007 | 1/30/2007 1:27:20 PM | P | CANC |
|
|
ron; Phone #: ###-#### Internet Inspection Request from: Victoria Beall see added r/i p/s
|
ELE07-00326
| Rough-In Permanent Service | 1/30/2007 | 1/30/2007 | 1/30/2007 1:26:54 PM | P | PASS |
|
|
ron; Phone #: ###-#### Internet Inspection Request from: Victoria Beall r/i p/s u/g new ok
|
ELE06-03350
| Final | 1/30/2007 | 1/30/2007 | 1/30/2007 12:45:25 PM | P | NR |
|
|
Re-Do Final please. Journeyman on site - Randy ###-####. Thank you Phone #: ###-#### met with contr, needs to address lights and shelves in closets
|
ELE07-00082
| Conference | 1/30/2007 | 1/30/2007 | 1/30/2007 10:59:33 AM | A | DONE |
|
|
met with UL and contr concerning changing fixtures in jewelry dept.
|
ELE07-00137
| Electrical Rough-In | 1/29/2007 | 1/30/2007 | 1/30/2007 10:46:36 AM | A | FAIL |
|
|
mike; Phone #: ###-#### call for key location Internet Inspection Request from: Victoria Beall corr. posted 300.4 shall provide 11/4" for cables parallel to framing members, 314.16 box fill cutin box hallway, 210.11(C)(3) &52(D) 20 amp circuit for bath recepts, 300.14 short grd wires, 110.14(B) grd wire crimp sleeves loose shall use listed tool or use wirenuts, called 3 times phone busy
|
ELE06-04593
| Electrical Rough-In | 1/29/2007 | 1/30/2007 | 1/30/2007 10:03:53 AM | A | PASS |
|
|
jeff; Phone #: ###-#### Internet Inspection Request from: Victoria Beall r/i ok
|
ELE06-04530
| Final | 1/29/2007 | 1/30/2007 | 1/30/2007 9:17:47 AM | A | PASS |
|
|
kevin; Phone #: ###-#### Note: please call for access Internet Inspection Request from: Cathy Chiles ok
|
ELE06-04673
| Electrical Rough-In | 1/30/2007 | 1/30/2007 | 1/30/2007 8:39:44 AM | A | PART |
|
|
Phone #: ###-#### r/i ok
|
ELE06-04042
| ELE-Aging Inspection | 1/30/2007 | 1/30/2007 | 1/30/2007 7:59:59 AM | | PART |
|
|
wsuc
|
ELE07-00046
| Electrical Rough-In | 1/29/2007 | 1/30/2007 | 1/29/2007 3:17:17 PM | A | CANC |
|
|
Reinspection of underground. If there are any problems please contact Marvin Miller. Thank you. Phone #: ###-#### Inspection cancelled from web by: Laura Longshaw
|