Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-00482 Conference1/30/20071/30/20071/30/2007 3:09:52 PMPDONE
stopped at job site wsuc
ELE06-03996 Final1/29/20071/30/20071/30/2007 2:46:50 PMPNH
if locked please call for access code at- ###-#### thanks Phone #: ###-####
called no access to front unit code would not work back unit ok both units need panel directory to be specific to location purpose and use 408.4
ELE06-01186 Electrical Rough-In1/30/20071/30/20071/30/2007 2:21:46 PMPPASS
elijah; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles r/i ok
ELE07-00278 Final1/30/20071/30/20071/30/2007 1:57:42 PMPPASS
paul; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles final ok
ELE07-00278 Electrical Rough-In1/30/20071/30/20071/30/2007 1:57:20 PMPPASS
paul; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
ELE07-00326 Electrical Rough-In1/30/20071/30/20071/30/2007 1:27:20 PMPCANC
ron; Phone #: ###-#### Internet Inspection Request from: Victoria Beall see added r/i p/s
ELE07-00326 Rough-In Permanent Service1/30/20071/30/20071/30/2007 1:26:54 PMPPASS
ron; Phone #: ###-#### Internet Inspection Request from: Victoria Beall r/i p/s u/g new ok
ELE06-03350 Final1/30/20071/30/20071/30/2007 12:45:25 PMPNR
Re-Do Final please. Journeyman on site - Randy ###-####. Thank you Phone #: ###-#### met with contr, needs to address lights and shelves in closets
ELE07-00082 Conference1/30/20071/30/20071/30/2007 10:59:33 AMADONE
met with UL and contr concerning changing fixtures in jewelry dept.
ELE07-00137 Electrical Rough-In1/29/20071/30/20071/30/2007 10:46:36 AMAFAIL
mike; Phone #: ###-#### call for key location Internet Inspection Request from: Victoria Beall corr. posted 300.4 shall provide 11/4" for cables parallel to framing members, 314.16 box fill cutin box hallway, 210.11(C)(3) &52(D) 20 amp circuit for bath recepts, 300.14 short grd wires, 110.14(B) grd wire crimp sleeves loose shall use listed tool or use wirenuts, called 3 times phone busy
ELE06-04593 Electrical Rough-In1/29/20071/30/20071/30/2007 10:03:53 AMAPASS
jeff; Phone #: ###-#### Internet Inspection Request from: Victoria Beall r/i ok
ELE06-04530 Final1/29/20071/30/20071/30/2007 9:17:47 AMAPASS
kevin; Phone #: ###-#### Note: please call for access Internet Inspection Request from: Cathy Chiles ok
ELE06-04673 Electrical Rough-In1/30/20071/30/20071/30/2007 8:39:44 AMAPART
Phone #: ###-#### r/i ok
ELE06-04042 ELE-Aging Inspection1/30/20071/30/20071/30/2007 7:59:59 AM PART
wsuc
ELE07-00046 Electrical Rough-In1/29/20071/30/20071/29/2007 3:17:17 PMACANC
Reinspection of underground. If there are any problems please contact Marvin Miller. Thank you. Phone #: ###-#### Inspection cancelled from web by: Laura Longshaw