Inspections for the day of: Tuesday, January 30, 2007.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-03232 ELE-Aging Inspection1/29/20071/30/20071/31/2007 2:34:27 PMADONE
called contr to see about calling for inspection
ELE07-00082 Final1/30/20071/30/20071/30/2007 3:53:30 PMPPASS
bob; Phone #: ###-#### Internet Inspection Request from: Victoria Beall 315 talked to field evaluation people, ok to final
ELE07-00331 Electrical Rough-In1/30/20071/30/20071/30/2007 3:02:38 PMPFAIL
NEIL; Phone #: ###-#### Internet Inspection Request from: Victoria Beall called, left corr notice, nec 338.10 & 334 se cable shall be secured within 12" of box, 300.4(D) nm cable shall be 1 1/4" from edge of framing member, 210.52(E) shall provide front outdoor recpt, 210.53(D)(2) water pipe ground shall be supplemented by additional electrode per 250.52(A)(2) thru (A)(7), BCC all make-up shall be done-switch ring in north bedroom
ELE07-00310 Final1/29/20071/30/20071/30/2007 2:57:00 PMPFAIL
carl; Phone #: ###-#### Internet Inspection Request from: Darla Downs called contr, left corr notice, BCC 4-05-33(A)(B) all equipment shall be listed by a nationally recognized testing laboratory, nec 110.3(A)(B) all elect equip shall be listed and labelled, NOTE: corrections shall be made in 2 weeks or further action will be taken, such as removal of power
ELE07-00146 Permanent Service1/24/20071/30/20071/30/2007 2:43:19 PMPPASS
###-#### Kendel p/s u/g n ok
ELE06-00320 Electrical Rough-In1/30/20071/30/20071/30/2007 1:44:21 PMPFAIL
robert; Phone #: ###-#### Internet Inspection Request from: Darla Downs met owner, left corr notice, nec 300.4(A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing members, 314.20 boxes shall be flush with finished surface, 314.17(C) nm cable shall be stapled within 8" of box, NOTE: upgrade permit to 19 rooms
ELE07-00327 Electrical Rough-In1/30/20071/30/20071/30/2007 1:41:13 PMPCANC
RON; Phone #: ###-#### Internet Inspection Request from: Victoria Beall see rip
ELE07-00327 Rough-In Permanent Service1/30/20071/30/20071/30/2007 1:40:55 PMPPASS
RON; Phone #: ###-#### Internet Inspection Request from: Victoria callede, left survey, 210.52(A)(1) shall add recpt in comp room, 334.30 shall staple nm within 12" of box, ric ok, p/s u/g n ok
ELE07-00046 Electrical Rough-In1/29/20071/30/20071/30/2007 10:56:39 AMAPASS
Reinspection of underground. Please notify Noah with any problems. Thank you. Phone #: ###-#### corr made, ok to cover u/g onlly
ELE05-04325 Final1/29/20071/30/20071/30/2007 10:44:07 AMAPART
Jason; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt 4th floor, south side rooms ok
ELE07-00268 Electrical Rough-In1/29/20071/30/20071/30/2007 9:52:41 AMAFAIL
Scheduled by a contractor via Hello! on 1/29/2007 at 3:23:22 PM. Contact: ###-####. called contr, left corr notice, nec 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 250.86 metal box shall be grounded
ELE06-02092 Permanent Service1/30/20071/30/20071/30/2007 9:50:23 AMAFAIL
Gary - ###-#### ok per Bob to put in for this am as he had an inspection there already///dld called, left corr notice, nec 408.4 circuit directory shall be complete, concise, clear, 348.30 fmc shall be strapped within 12" of box, 358.30 emt shall be strapped within 3' of box, 314.15 fittings in wet locations shall be listed for use in wet locations,314.28(C) covers shall be provided with suitable screws,BCC all make-up shall be done, range and dryer shall be 4-wire circuits
ELE05-01443 Final1/29/20071/30/20071/30/2007 8:46:59 AMAPASS
PAUL; Phone #: ###-#### Internet Inspection Request from: Darla Downs ok to final
ELE05-02003 Final1/29/20071/30/20071/30/2007 8:11:52 AMAPART
Scheduled by a contractor via Hello! on 1/29/2007 at 4:32:02 PM. Contact: ###-####. pool light potting ok, a/c listed ok, pump gone ok