BLD06-03073
| BLD-Other | 1/30/2007 | 1/30/2007 | 1/31/2007 7:39:09 AM | P | PASS |
|
|
life safety finaled
|
FIR06-00806
| FIR-Aging Inspection | 1/30/2007 | 1/30/2007 | 1/30/2007 3:27:17 PM | | NR |
|
|
work is in progress
|
FIR06-00755
| INSP-Sprinkler Rough-in/Hydro | 1/30/2007 | 1/30/2007 | 1/30/2007 3:24:30 PM | P | CANC |
|
|
Per Terry the test is not ready today because the test pump had a malfunction.
|
FIR07-00062
| INSP-Final Inspection | 1/30/2007 | 1/30/2007 | 1/30/2007 2:51:53 PM | P | PASS |
|
|
permit finaled
|
FIR05-00644
| INSP-Sprinkler Rough-in/Hydro | 1/29/2007 | 1/30/2007 | 1/30/2007 2:18:40 PM | A | PASS |
|
|
The standpipe hydro test passed. Started the 24 hour air tests on both dry systems at 9:30. The 4th floor is at 45psi and the front system is at 47psi.
|
FIR06-00592
| INSP-Final Inspection | 1/29/2007 | 1/30/2007 | 1/30/2007 1:24:17 PM | P | FAIL |
|
|
No actual inspection was performed. I went through notification devices. Some need to be at a higher candella. The NAC panel has been relocated to the second floor. The smoke detector at this NAC needs relocated to the roof deck. As builts are required at the time of the next inspection. There appears to be a access controlled egress system at the doors which will need to be addressed.
|
BLD05-02149
| FIRE-Final Inspection | 1/30/2007 | 1/30/2007 | 1/30/2007 11:44:31 AM | P | PASS |
|
|
life safety finaled
|
FIR06-00591
| INSP-Sprinkler Rough-in/Hydro | 1/29/2007 | 1/30/2007 | 1/30/2007 11:01:45 AM | A | PART |
|
|
Hydro test was not ready. Rooms with ceilings are ok to cover
|
FIR06-00955
| INSP-Sprinkler Rough-in | 1/29/2007 | 1/30/2007 | 1/30/2007 9:56:37 AM | A | PASS |
|
|
Underground piping is ok to cover
|