Inspections for the day of: Wednesday, January 30, 2008.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD07-02824 FIRE-Final Inspection1/29/20081/30/20081/31/2008 8:04:14 AMPPASS
Fire life safety is satisfactory, fire alarm final inspection completed in conjunction with site visit.
FIR07-00953 INSP-Final Inspection1/30/20081/30/20081/31/2008 8:02:03 AMPPASS
Fire alarm permit finaled.
BLD07-03109 FIRE-Final Inspection1/29/20081/30/20081/31/2008 8:01:36 AMPPASS
Fire life safety inspection passed.
BLD07-02755 FIRE-Final Inspection1/29/20081/30/20081/31/2008 8:01:01 AMAFAIL
Provide manual mag unlock device "push to exit" at one location, missing one fire extinguisher, need to final project related fire alarm permit.
FIR08-00031 INSP-Sprinkler Rough-in1/30/20081/30/20081/30/2008 2:52:24 PMPPART
OH rough-in inspection completed, attatchments and installation appears acceptable however final head location cannot be approved at this time due to lacking walls at all areas which are not yet constructed at this time.
FIR04-00674 INSP-Final Inspection1/30/20081/30/20081/30/2008 1:53:12 PMPPASS
Fire sprinkler permit finaled.
FIR07-01039 INSP-Final Inspection1/30/20081/30/20081/30/2008 1:49:20 PMPPASS
Fire sprinkler permit finaled.
FIR07-01039 INSP-Sprinkler Rough-in/Hydro1/29/20081/30/20081/30/2008 12:06:51 PMAPASS
System main tie-in verified for completion, old branch lines and head demo at the permit work area is also complete.
FIR07-01039 INSP-Final Inspection1/30/20081/30/20081/30/2008 11:56:00 AMPCANC
Scheduled by a contractor via Hello! on 1/29/2008 at 2:29:37 PM. Contact: ###-####.
BLD07-03065 FIRE-Final Inspection1/29/20081/30/20081/30/2008 11:27:50 AMAPASS
Fire life safety inspection passed per site visit on 1/24.
FIR08-00011 INSP-Final Inspection1/30/20081/30/20081/30/2008 11:20:13 AMAPASS
Field modifications are acceptable, as-built plans accepted.
FIR07-00827 INSP-Sprinkler Rough-in/Hydro1/29/20081/30/20081/30/2008 11:06:50 AMAPART
See annotations on plan dated 1/28 for areas okayed for cover.
FIR07-00920 INSP-Final Inspection1/29/20081/30/20081/30/2008 11:03:08 AMAPASS
Fire sprinkler permit finaled.
FIR07-00869 FIR-Aging Inspection1/30/20081/30/20081/30/2008 11:01:22 AM DEFR
Pending site inspection request.
FIR07-00662 INSP-Alarm Testing1/29/20081/30/20081/30/2008 12:00:00 AMADEFR
Talk to Rand with Alarm Star About the issues of A/V devices being to low. Pull stations to high and the wrong (CD) for the devices in th ADA rooms.KR
FIR07-00953 INSP-Final Inspection1/29/20081/30/20081/29/2008 4:30:44 PMPPART
See approved set of plans for red lined areas approved for cover. KR