Inspections for the day of: Wednesday, January 30, 2008.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00934 INSP-Final Inspection1/30/20081/30/20081/30/2008 5:10:36 PMPFAIL
Nozzles had not been installed in the plenum as required by Ansul. Inspection was stopped until this work is completed on both hoods.
FIR07-01033 INSP-Final Inspection1/29/20081/30/20081/30/2008 5:09:20 PMPFAIL
The hood inspection could not be completed therefore the fire alarm could not be completed.
FIR07-00874 INSP-Sprinkler Rough-in1/30/20081/30/20081/30/2008 5:07:02 PMPPASS
The tenting/insulation for the south wing is acceptable. Piping still can not be covered since the stop work order for the fire alarm system still stands.
FIR07-01046 INSP-Final Inspection1/30/20081/30/20081/30/2008 4:24:43 PMPPASS
permit finaled
FIR07-01046 INSP-Sprinkler Rough-in/Hydro1/30/20081/30/20081/30/2008 4:23:51 PMPPASS
Permit finaled
FIR07-00484 INSP-Sprinkler Rough-in/Hydro1/29/20081/30/20081/30/2008 1:28:19 PMPPASS
The underground hydro test passed.
FIR06-00011 INSP-Alarm Testing1/30/20081/30/20081/30/2008 12:20:39 PMPFAIL
The test today was for the cafeteria area. When the pull station was pulled no alarms sounded. No other testing was performed. Test is to be rescheduled for monday.
BLD08-00090 FIRE-Final Inspection1/29/20081/30/20081/30/2008 11:33:56 AMAPASS
fire life safety passed
FIR07-00904 INSP-Alarm Testing1/29/20081/30/20081/30/2008 11:33:07 AMAPASS
permit finaled
FIR08-00062 INSP-Final Inspection1/29/20081/30/20081/29/2008 2:45:42 PMAPASS
Permit finaled. The additional pendant has been added.