Inspections for the day of: Friday, January 30, 2009.
Number of inspections: 12
Percentage of inspections complete: 92 %
Percentage of inspections not complete: 8 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00901 INSP-Conference1/28/20091/29/2009 A 
FIR09-00024 INSP-Final Inspection1/29/20091/30/20092/2/2009 11:25:58 AMAPASS
Field inspection completed satisfactory.
FIR08-00699 INSP-Sprinkler Rough-in1/30/20091/30/20091/30/2009 4:52:32 PMPPART
OH installation at classroom wing as marked on plan set sheet FP2 including exceptions okayed for cover.
FIR08-00801 INSP-Supply line flush1/30/20091/30/20091/30/2009 3:59:53 PMPPART
UG fire supply line flush completed satisfactory.
BLD08-00289 FIRE-Final Inspection1/30/20091/30/20091/30/2009 2:16:58 PMPPASS
Fire final okay.
FIR08-00567 INSP-Final Inspection1/30/20091/30/20091/30/2009 2:15:55 PMPPASS
Fire sprinkler permit finaled.
FIR08-00567 INSP-Sprinkler Rough-in/Hydro1/30/20091/30/20091/30/2009 2:15:29 PMPPASS
Corrections field verified, inspection passed.
FIR08-00826 INSP-Final Inspection1/29/20091/30/20091/30/2009 1:41:37 PMPPASS
Fire alarm inspection and testing passed, permit finaled.
FIR08-00815 INSP-Supply line flush1/29/20091/30/20091/30/2009 1:40:52 PMAPART
Inspection intended for OH cover at the main entry vestibule- cover approved, discussed freeze protection for piping installed- will need stamped plan set on site at next site visit.
BLD08-01257 FIRE-Final Inspection1/29/20091/30/20091/30/2009 10:14:53 AMPFAIL
Missing max occupant load signs at three areas, one fire extinguisher has not been provided, need to install missing ceiling tiles at the comm. room and one classroom. Exit signs and EM lighting tested okay. Scope of permit work is not yet complete at the east side hallway and two classrooms including the new access control door in the corridor which will require a fire alarm permit for interconnection to the building FACP. See fire code review notes and plan annotations for details.
FIR08-00641 INSP-Final Inspection1/29/20091/30/20091/30/2009 10:09:38 AMAPASS
Fire sprinkler permit okay for final per scope of work.
BLD08-01430 FIRE-Final Inspection1/29/20091/30/20091/30/2009 9:44:34 AMAPASS
Correction notice items verified for compliance, final fire life safety inspection passed.