Inspections for the day of: Friday, January 30, 2009.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD08-02580 FIRE-Final Inspection1/29/20091/30/20091/30/2009 3:44:14 PMAFAIL
This inspection was just for the cooler which is fine. I went over other requirements for phase I sign off which includes approved hardware on the office doors and the back exit door, location of fire extinguishers and exit sign/emergency light locations.
BLD07-01941 FIRE-Final Inspection1/30/20091/30/20091/30/2009 1:27:26 PMPPASS
Life safety passed.
BLD07-01941 FIRE-Final Inspection1/29/20091/30/20091/30/2009 12:59:53 PMAPASS
Life safety passed. The builder lowered the rack shelving to provide the 24" minimum clearance.
BLD08-01299 FIRE-Final Inspection1/30/20091/30/20091/30/2009 12:51:45 PMPPASS
life safety passed.
BLD08-00684 FIRE-Final Inspection1/30/20091/30/20091/30/2009 12:51:10 PMPPASS
LIfe safety passed
BLD09-00090 FIRE-Final Inspection1/29/20091/30/20091/30/2009 12:49:21 PMAPART
A temporary occupancy was given. Provide approved hardware for the exit door which includes removing the thumbturn lock and the round knob. Also provide the annual inspection for the fire extinguisher.
FIR08-00810 INSP-Final Inspection1/29/20091/30/20091/30/2009 10:14:59 AMAFAIL
The city approved plans do not reflect the actual installation. Instead of one new point there are two and a supervisory signal from the vesda is connected directly to the wireless dialer which is not allowed. Provide as-builts and wire the panels correctly.
FIR07-01032 INSP-Sprinkler Rough-in/Hydro1/29/20091/30/20091/30/2009 10:12:07 AMAPASS
The hydro test for the second floor skilled nurse dining area passed.