Inspections for the day of: Monday, January 30, 2012.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD11-02898 FIRE-Final Inspection1/27/20121/30/20121/30/2012 3:50:02 PMPPASS
life safety passed
BLD12-00132 FIRE-Final Inspection1/30/20121/30/20121/30/2012 3:01:41 PMPFAIL
Provide single action hardware on the rear exit door and repair the exit sign/emergency light located directly above this door.
BLD11-02911 FIRE-Final Inspection1/30/20121/30/20121/30/2012 3:00:40 PMPPASS
Life safety passed. An additional fire extinguisher is required on the second floor. Per Elizabeth the fire extinguisher would be installed prior to the building inspector sign off.
FIR12-00004 INSP-Final Inspection1/25/20121/30/20121/30/2012 2:04:12 PMPPASS
permit finaled
FIR11-00563 INSP-Sprinkler Rough-in/Hydro1/27/20121/30/20121/30/2012 2:03:25 PMAPASS
See the city approved plans for the specific rooms where sprinkler piping can be covered. The include the rooms at the west end of the third floor.
BLD11-02455 FIRE-Conference1/27/20121/30/20121/30/2012 1:28:48 PMADONE
On site visit with contractor regarding fire code review note items and project finish schedule.
BLD11-01891 FIRE-Final Inspection1/27/20121/30/20121/30/2012 10:27:51 AMAPASS
life safety passed
BLD12-00116 FIRE-Final Inspection1/30/20121/30/20121/30/2012 9:47:18 AMPPASS
life safety passed