Inspections for the day of: Thursday, January 30, 2014.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-01720 ELE-Aging Inspection1/30/20141/30/20141/31/2014 3:04:12 PM DONE
Waiting on owner
ELE13-03155 Final1/30/20141/30/20141/30/2014 4:12:13 PMPFAIL
Clyde Phone #: ###-#### 410.10(A)- Fan/light combo rated for shower if GFCI protected, GFCI located in up hall and pantry. Need to confirm.
408.38-Panel cover shall be securely fastened.
314.23- Receptical outlet located at end of peninsula shall be securely fastened
ELE13-03154 Final1/30/20141/30/20141/30/2014 3:57:47 PMPFAIL
Clyde Phone #: ###-#### 410.10(A)- Recessed luminaire located above shower/tubs shall be listed wet location so water will not accumulate above trim. Confirmed listing for fixture located in shower area if GFCI protected. GFCI device for upstairs in hallway and main level GFCI located in pantry.
ELE13-03498 Final1/30/20141/30/20141/30/2014 3:05:37 PMPPASS
Lockbox is 3811. Thank You Phone #: ###-#### >> Inspection requested via web by Clay Morgan Final ok
GCE13-00181 GCE-Rough-In1/30/20141/30/20141/30/2014 2:21:05 PMPPASS
Mark ###-#### Walls complete. Wall rough in ok cover
GCE14-00017 GCE-Final1/29/20141/30/20141/30/2014 1:29:15 PMAPASS
Jeff ###-#### Service recconnect final ok
GCE14-00017 GCE-Permanent Service1/30/20141/30/20141/30/2014 1:28:52 PMPPASS
Jeff ###-#### p/s o/h rec ok
ELE13-03338 Final1/29/20141/30/20141/30/2014 1:07:14 PMAPASS
Please give one hour notice to insure access to job. thank you. ###-#### Phone #: ###-#### >> Inspection requested via web by Jerry Moore Final ok
ELE13-03550 Final1/30/20141/30/20141/30/2014 12:49:15 PMPFAIL
kevin Phone #: ###-#### 110.26- Minimum work space shall be provided for solar panels in basement. 36" minimum depth
ELE13-00614 Electrical Rough-In1/30/20141/30/20141/30/2014 11:01:16 AMPPASS
Walls behind reception area. reception area done under different permit. Phone #: ###-#### >> Inspection requested via web by Mark M Wall rough in ok cover
ELE14-00045 Electrical Rough-In1/30/20141/30/20141/30/2014 10:58:23 AMPPASS
Contact: Wes Powell. Ceiling rough-in please Phone #: ###-#### >> Inspection requested via web by Deb Gooden Center hard lid west. Ceiling rough in ok cover
ELE14-00183 Electrical Rough-In1/29/20141/30/20141/30/2014 10:37:18 AMAPASS
Contact: Justin Hugo. underground inspection please Phone #: ###-#### >> Inspection requested via web by Deb Gooden Due to solid rock in trench 300.5 note 5 where burial depth can not be acheived direct burial conduits shall be completely embedded in min of 2" of concrete. Under ground rough in ok cover
ELE13-03452 Electrical Rough-In1/29/20141/30/20141/30/2014 10:15:34 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Ron Zimmerman Upper walls rough in ok cover
ELE14-00033 Electrical Rough-In1/29/20141/30/20141/30/2014 9:51:23 AMAPASS
joe - radiant floor inspection - early morning please Phone #: ###-#### Suntouch t-stat checked for class A GFCI confirmed. Floor heat rough in ok cover
ELE13-01861 Final1/29/20141/30/20141/30/2014 9:24:40 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Mark M Final ok
ELE13-01001 Final1/29/20141/30/20141/30/2014 9:14:40 AMAPASS
cell ###-#### Phone #: ###-#### >> Inspection requested via web by Mark M Final ok
ELE13-03437 Final1/29/20141/30/20141/30/2014 9:13:51 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Mark M Final ok