ELE12-02127
| ELE-Aging Inspection | 1/30/2015 | 1/30/2015 | 2/4/2015 6:42:24 AM | | CANC |
|
|
too busy
|
ELE12-00814
| ELE-Aging Inspection | 1/30/2015 | 1/30/2015 | 2/4/2015 6:42:04 AM | | CANC |
|
|
too busy
|
GCE15-00015
| GCE-Temporary Service | 1/29/2015 | 1/30/2015 | 1/30/2015 4:01:56 PM | A | PASS |
|
|
Terry ###-#### t/s u/g n ok
|
ELE13-03105
| Permanent Service | 1/30/2015 | 1/30/2015 | 1/30/2015 3:43:23 PM | P | FAIL |
|
|
Ras bldg service Phone #: ###-#### Inspection requested via web by matt miller 110.26(C)(3)- Where equiptment rated 1200A or more that contain overcurrent devices personnel door shall have panic hardware.
|
ELE15-00192
| Electrical Rough-In | 1/26/2015 | 1/30/2015 | 1/30/2015 2:20:03 PM | P | FAIL |
|
|
Charles-please call prior Phone #: ###-#### Finished basement a rec room and bed without pulling permits in 2007. Bathroom completed when house originally built in 2004. 210.12(A)- All outlets in dwelling unit bedroom areas shall have AFCI protection. 406.12- All receptical outlets installed in a dwelling unit shall be tamper resistant type.
|
ELE14-01066
| Permanent Service | 1/30/2015 | 1/30/2015 | 1/30/2015 1:27:43 PM | P | PASS |
|
|
Lonnie ###-#### BLD13-00184 for building H, 208 volt service fed from TB18 and 480 volt service fed rrom TB19. p/s u/g n ok
|
ELE14-01814
| Electrical Rough-In | 1/29/2015 | 1/30/2015 | 1/30/2015 1:23:56 PM | P | PASS |
|
|
Wall rough-in inspection for IL area ''D'' garage rooms: PD5 Resident Storage and PD6 Storage. Building permit number BLD13-00182. Call Lonny when on-site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum Storage rooms as described in basement wall rough in ok cover
|
ELE15-00245
| Temporary Service | 1/29/2015 | 1/30/2015 | 1/30/2015 12:15:39 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE15-00246
| Temporary Service | 1/29/2015 | 1/30/2015 | 1/30/2015 12:15:11 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE15-00244
| Temporary Service | 1/29/2015 | 1/30/2015 | 1/30/2015 12:14:35 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE15-00248
| Temporary Service | 1/29/2015 | 1/30/2015 | 1/30/2015 12:14:06 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE15-00243
| Temporary Service | 1/29/2015 | 1/30/2015 | 1/30/2015 12:13:31 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE15-00190
| Electrical Rough-In | 1/30/2015 | 1/30/2015 | 1/30/2015 11:14:35 AM | P | PASS |
|
|
back of house walls Phone #: ###-#### Inspection requested via web by Bryan McLaughlin Wall rough in ok cover
|
ELE14-03551
| Final | 1/29/2015 | 1/30/2015 | 1/30/2015 11:14:00 AM | A | PASS |
|
|
late morning please Phone #: ###-#### Inspection requested via web by Bryan McLaughlin Final ok
|
ELE15-00253
| Permanent Service | 1/29/2015 | 1/30/2015 | 1/30/2015 10:46:55 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt p/s o/h rec ok
|
ELE14-03385
| Electrical Rough-In | 1/29/2015 | 1/30/2015 | 1/30/2015 10:28:16 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Walls, soffits, and hardlids rough in ok cover
|
ELE13-03105
| Permanent Service | 1/29/2015 | 1/30/2015 | 1/30/2015 10:04:41 AM | A | NH |
|
|
Ras service Phone #: ###-#### Inspection requested via web by matt miller No return phone call. Not sure where service is located on premisis
|
ELE15-00240
| Final | 1/29/2015 | 1/30/2015 | 1/30/2015 9:29:06 AM | A | PASS |
|
|
Mobile home connection Phone #: ###-#### Inspection requested via web by jamie berg Mobile home service and AC prewire Final ok
|
ELE15-00240
| Rough-In Permanent Service | 1/30/2015 | 1/30/2015 | 1/30/2015 9:23:46 AM | P | PASS |
|
|
Mobile home connection Phone #: ###-#### Inspection requested via web by jamie berg Mobile home service rough in ok. p/s u/g rec ok
|
ELE15-00186
| Final | 1/28/2015 | 1/30/2015 | 1/30/2015 9:08:28 AM | A | NH |
|
|
Phone #: ###-#### Inspection requested via web by Randy Fletcher No answer at door. Will reschedule
|
ELE14-02473
| Final | 1/29/2015 | 1/30/2015 | 1/30/2015 8:45:59 AM | A | PASS |
|
|
Call ###-#### for access Phone #: ###-#### Inspection requested via web by Heath Thomas Final ok
|
ELE14-02474
| Final | 1/29/2015 | 1/30/2015 | 1/30/2015 8:45:30 AM | A | PASS |
|
|
Call ###-#### for access Phone #: ###-#### Inspection requested via web by Heath Thomas Final ok
|
ELE14-02263
| Final | 1/29/2015 | 1/30/2015 | 1/30/2015 8:44:59 AM | A | PASS |
|
|
Call ###-#### for access Phone #: ###-#### Inspection requested via web by Heath Thomas Final ok
|
ELE15-00188
| Electrical Rough-In | 1/29/2015 | 1/30/2015 | 1/30/2015 8:03:39 AM | A | PASS |
|
|
CEILING ROUGH IN Phone #: ###-#### Inspection requested via web by JENNY EMEL Hard lids complete rough in ok cover
|