BLD13-01820
| FIRE-Sprinkler Rough-in | 1/30/2015 | 1/30/2015 | 1/30/2015 2:59:48 PM | P | FAIL |
|
|
Provide approval from plan review for the road surface change, remove thumbturn dead bolts and provide annual inspection tag for fire extinguishers.
|
FIR15-00011
| INSP-Sprinkler Rough-in | 1/30/2015 | 1/30/2015 | 1/30/2015 2:51:51 PM | P | PASS |
|
|
See the city approved plans for areas where piping above hardlids can be covered.
|
FIR14-00518
| INSP-Final Inspection | 1/29/2015 | 1/30/2015 | 1/30/2015 2:47:54 PM | A | FAIL |
|
|
Need plan modificatios and the hvac unit/shut down addressed.
|
FIR14-00895
| INSP-Final Inspection | 1/28/2015 | 1/30/2015 | 1/30/2015 12:10:13 PM | A | FAIL |
|
|
Everything tested ok except the access control system needs to be connected to the FACP as per IFC Chapter 10. As-builts showing this work as well as the candella changes in the Lobby and Office will be required prior to a final sign off.
|
BLD14-00948
| FIRE-Final Inspection | 1/29/2015 | 1/30/2015 | 1/30/2015 9:56:48 AM | A | PART |
|
|
Phase one life safety is complete (New shop/Office Area). Need parking lot/fire dept access completed (being bonded) and the air compressor room completed
|
BLD14-03523
| FIRE-Final Inspection | 1/30/2015 | 1/30/2015 | 1/30/2015 9:41:14 AM | P | CANC |
|
|
Arrielle Dreher will be the onsite contact. Thank you Phone #: ###-#### >> Inspection requested via web by Megan Swift Inspection cancelled from web by: Megan Swift
|
FIR14-00745
| INSP-Final Inspection | 1/29/2015 | 1/30/2015 | 1/30/2015 9:13:39 AM | A | PASS |
|
|
Permit finaled
|
FIR15-00018
| INSP-Final Inspection | 1/29/2015 | 1/30/2015 | 1/30/2015 9:12:14 AM | A | PASS |
|
|
Permit finaled
|
BLD15-00066
| FIRE-Final Inspection | 1/29/2015 | 1/30/2015 | 1/30/2015 9:11:53 AM | A | PASS |
|
|
Life safety passed
|
FIR15-00017
| INSP-Final Inspection | 1/29/2015 | 1/30/2015 | 1/30/2015 9:11:14 AM | A | PASS |
|
|
Permit finaled
|
FIR14-00518
| INSP-Final Inspection | 1/29/2015 | 1/30/2015 | 1/29/2015 12:34:30 PM | A | CANC |
|
|
Please notify Greg 30 min. prior to arrival. Thank you! Phone #: ###-#### >> Inspection requested via web by Stacie Tasker Inspection cancelled from web by: Stacie Tasker
|