Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-04115 Final1/27/20171/30/20171/30/2017 3:08:09 PMPFAIL
would like call ahead Phone #: ###-####
Homeowner took over complete trim out of work shop. No conference requested.
210.8- GFCI receptacles shall be located in readily accessible locations. To move GFCI behind refrigerator to over counter.
210.8(A)(3)- Back receptacle located in 2 gang and front receptacles not GFCI protected, they shall be.
210.52(B)(2)- Small appliance circuit shall not feed outdoor receptacles.
230.70- A means shall be provided to disconnect all conductors from a structure. Need main disconnect for work shop.
406.9- Outdoor receptacles exposed to weather shall have heavy duty in use cover installed. Front.
406.9(B)- Front outdoor receptacle shall be tamper and weather resistant type.
406.9 ex.- Receptacles located above 5'5" not required to be temper resistant type. Microwave.
406.12- Tamper resistant receptacles shall be installed through out work shop.
ELE17-00220 Electrical Rough-In1/30/20171/30/20171/30/2017 1:55:48 PMPPASS
Herb should be there ###-#### Phone #: ###-#### Inspection requested via web by Clay Morgan
Bath and laundry changed locations. Need to check splice at old dryer location in bath under vanity aluminum/ copper.
Rough in ok cover
ELE17-00215 Final1/27/20171/30/20171/30/2017 12:46:09 PMAPASS
Phone #: ###-#### Final ok
ELE16-01667 Electrical Rough-In1/30/20171/30/20171/30/2017 9:56:52 AMAPASS
Reinspect storage walls and stairwell #3 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Storage rm and corridor, and stair 3 walls 2nd floor rough in ok cover
ELE16-04064 Final1/27/20171/30/20171/30/2017 8:47:32 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok