Inspections for the day of: Monday, January 30, 2017.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00718 INSP-Final Inspection1/30/20171/30/20171/30/2017 2:10:17 PMPPASS
permit finaled
BLD16-00390 FIRE-Final Inspection1/30/20171/30/20171/30/2017 1:06:48 PMPPASS
life safety passed
FIR16-00803 INSP-Sprinkler Rough-in1/27/20171/30/20171/30/2017 11:47:27 AMAPART
The latest approved plans need to be on site that show the actual project details, retaining straps need to be installed, hangers that are installed need to actually support the pipe, additional coverage is needed at the east end of the new offices. Piping is ok to cover.
FIR16-00813 INSP-Sprinkler Rough-in1/27/20171/30/20171/30/2017 10:41:39 AMAPASS
Rough-in passed. Piping can be covered.
FIR16-00798 INSP-Sprinkler Rough-in1/27/20171/30/20171/30/2017 8:18:37 AMAPASS
Remaining piping in the Conference Room is ok to cover.
FIR17-00044 INSP-Sprinkler Rough-in1/27/20171/30/20171/30/2017 8:18:05 AMAPASS
Permit finaled