ELE20-00356
| Electrical Rough-In | 1/29/2020 | 1/30/2020 | 1/30/2020 2:43:31 PM | P | PASS |
|
|
Larry Phone #: ###-#### Detached garage in rear of lot had wiring removed from a wall and was exposed from upper wall to panel and entered panel between panel can and cover. All exposed wiring has been removed. Owner to safe off water heater circuit either in a box with a cover in the wall or install water heater and terminate in it. Although rough no life safety issues left to correct except water heater circuit and install panel cover.
|
ELE19-01489
| Electrical Rough-In | 1/29/2020 | 1/30/2020 | 1/30/2020 1:47:11 PM | P | PASS |
|
|
Ceiling/Canopy covers in area A and D. Toby is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Area (A) canopy and area (D) south grid rough in ok cover.
|
ELE19-04702
| Final | 1/29/2020 | 1/30/2020 | 1/30/2020 11:31:38 AM | A | FAIL |
|
|
access through alley to garage sliding door to garage should be open Phone #: ###-#### Inspection requested via web by steve sellers 310.16- Minimum size conductor for 60 amp overcurrent device is #6 copper conductor, #8 installed from house to garage.
|
ELE19-04106
| Final | 1/30/2020 | 1/30/2020 | 1/30/2020 10:53:53 AM | A | PASS |
|
|
garage code 4224 Phone #: ###-#### Inspection requested via web by Troy Ballard Final ok
|
ELE19-04040
| Final | 1/28/2020 | 1/30/2020 | 1/30/2020 10:01:33 AM | A | PASS |
|
|
door code is 4224 but the general Anthony is suppose to be there. ###-#### Any questions call Jerry ###-#### Phone #: ###-#### Inspection requested via web by Dave Brueggemann Final ok
|
ELE20-00277
| Electrical Rough-In | 1/28/2020 | 1/30/2020 | 1/30/2020 9:49:23 AM | A | PASS |
|
|
Matt. Wall cover. Phone #: ###-#### Inspection requested via web by Sean DeLacy Full height walls rough in ok cover.
|