FIR19-00890
| INSP-Sprinkler Rough-in | 1/30/2020 | 1/30/2020 | 1/30/2020 4:15:07 PM | P | PASS |
|
|
Previously noted items have been corrected, cover is approved.
Richard Phone #: ###-####
|
FIR19-00661
| INSP-Sprinkler Rough-in | 1/30/2020 | 1/30/2020 | 1/30/2020 4:14:34 PM | P | PASS |
|
|
Previously noted items have been corrected.
Phone #: ###-#### Inspection requested via web by Connie Danes
|
BLD19-04012
| FIRE-Final Inspection | 1/30/2020 | 1/30/2020 | 1/30/2020 3:43:28 PM | P | PASS |
|
|
No fire sprinkler modifications, fire alarm inspection is complete, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work complete, signatures provide on permit sign off card.
Zach Phone #: ###-####
|
FIR19-00959
| INSP-Sprinkler Rough-in | 1/30/2020 | 1/30/2020 | 1/30/2020 2:48:53 PM | P | FAIL |
|
|
Changes had to be made to head coverage due too beam layout, need to have city approved plans match what was installed.
Phone #: ###-#### Inspection requested via web by Jonathan LaFond
|
BLD19-04367
| FIRE-Final Inspection | 1/30/2020 | 1/30/2020 | 1/30/2020 1:51:34 PM | P | PASS |
|
|
Previously noted items have been corrected, no fire sprinklers, no fire alarms, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work complete, signature provided on perit sign off card.
Justin ###-####
|
FIR19-00702
| INSP-Sprinkler Rough-in | 1/30/2020 | 1/30/2020 | 1/30/2020 1:11:23 PM | P | CANC |
|
|
Inspection request was cancelled per conversation with point of contact due to flexible dry pendant being graded the wrong way. Corrections will be made to have whip grade towards sprinkler head per manufacturers requirements.
Rough and tenting on 1st, 3rd, and 4th floors. 2nd already passed. Please call James before heading out. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD19-04367
| FIRE-Final Inspection | 1/30/2020 | 1/30/2020 | 1/30/2020 11:29:58 AM | A | CANC |
|
|
Provide phone number for point of contact notification as requested in point of contact notes. Did not go to project site due to manpower issues, this request is canclled and inspection will need to be rescheduled with point of contact information.
Please notify me 15 minutes prior to arrival to ensure I''m on site. Inspection requested via web by Justin Schwartz
|
FIR19-00785
| INSP-Sprinkler Rough-in | 1/29/2020 | 1/30/2020 | 1/30/2020 11:25:29 AM | A | FAIL |
|
|
Southeast level 1 apartment has 2 heads that are more than 9 foot off of wall, city approved drawings show a maximum of 9 foot off of wall spacing. Inspection stopped on level 1. Looked at level 3 tenting at contractors request, found multiple areas where small amounts of pipe was exposed to attic space as well as BAT insulation resting on plumbing vent pipes provided an area for blow in insulation to compromise pocket between sheetrock and sprinkler piping, areas need corrected before cover can be approved. Grade needs to be maintained from adapter to flexible dry sprinkler as required by manufacturer specs, multiple dry heads had grade going back to adapter. Inspection stopped, a complete re-inspection will need to be performed due too deficiencies found in the first inspected areas on level 1 and 3.
To cover- Bill Phone #: ###-####
|
BLD19-02844
| FIRE-Final Inspection | 1/29/2020 | 1/30/2020 | 1/30/2020 10:34:58 AM | A | PART |
|
|
Reviewed plans are not in e-plan, blue prints were a paper print review. Floor plan has minor changes that need to be reflected on the city approved drawings. Provided the GC with the reviewers information for architect submittal. In field conditions are code compliant, city approved drawings need to reflect installed floor plan. 30 day TCO auhtorized for life fire safety, after plans are reviewed, acccepted and show floor plan changes then life fire safety can be finaled, signatures provided on permit sign off card.
Phone #: ###-#### Inspection requested via web by Steve Jones
|
FIR20-00032
| INSP-Final Inspection | 1/29/2020 | 1/30/2020 | 1/30/2020 9:52:29 AM | A | FAIL |
|
|
Dry sidewall in addition needs to comply with table 8.4.9.1 or provide an observed ambient temperature of vehicle bay to show what temperature the barrel length will be exposed too.
Contact: Steve Vaughn Phone #: ###-#### Inspection requested via web by Hunter Fillmore
|
BLD19-01906
| FIRE-Final Inspection | 1/29/2020 | 1/30/2020 | 1/30/2020 8:53:22 AM | A | FAIL |
|
|
Emergency lighting that is installed does not match what was submitted on city approved drawings, approved drawings need to reflect what is installed. Plans need to be corrected in the unoccupied suites, approved plans show emergency lighting in the ceiling grid, no grid is installed. During inspection fire alarm annunciator showed trouble, then trouble cleared, need to verify what caused trouble on fire alarm panel and repair as neccessary. Provide "Fire sprinkler riser room" signage on riser room door as discussed. Grading permit requires a signature for life fire safety, please schedule with next BLD life fire safety inspection. Provide exit sign that is shown on city approved drawings that was not in place at time of inspection.
Phone #: 2084073234 >> Inspection requested via mobile web by Allen
|