Inspections for the day of: Thursday, January 30, 2020.
Number of inspections: 1
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorGreg Ruxton
TitleFIRE CODE PLAN EXAMINER
Phone #208-608-7058
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
NAF19-00111 INSP-Final1/28/20201/30/20201/30/2020 2:43:57 PMPFAIL
Inspection stopped based on noted deficiencies. Exterior pull stations not listed for outdoor use, plans on site did not include Rm 111, a Knox Box was not installed, a copy of supervising station signal reports was not complete.

Contractor to change exterior pull stations, install Knox Box after consulting with Garden City Fire Department, provide updated map reflecting floor plan and all device locations and test 100 percent of devices and provide copy of supervising station reports.

John Howard, Technician Phone #: ###-#### Inspection requested via web by John Siewert