Inspections for the day of: Monday, January 31, 2005.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-00272 Temporary Service1/28/20051/31/20051/31/2005 12:00:00 AMAPASS
jim ###-#### corrections made, t/s o/h n ok 1/31/2005 8:01:38 AM
ELE04-04115 Final1/28/20051/31/20051/31/2005 12:00:00 AMAPASS
Internet Inspection Request from: Bob Glenn ok to final 1/31/2005 10:00:16 AM
ELE05-00187 Electrical Rough-In1/28/20051/31/20051/31/2005 12:00:00 AMAFAIL
jennifer; Phone #: ###-#### Internet Inspection Request from: Barbara Moore 300.4(D) cable shall 11/4" from edge, 334.23 cable shall be protected within 6' of hatch in attic, 334.24 bend radius 5 times diameter of cable, 334.30 and 314.17C cable shall be supported at intervals of 41/2' and within 8" of each box. Sheath shall be 1/4 " in box. Cable shall not be stapled on edge., 314.29 Junction boxes shall be accessible in attic. 1/31/2005 9:48:10 AM 1/31/2005 9:48:16 AM
ELE04-04034 Final1/31/20051/31/20051/31/2005 12:00:00 AMPPASS
Phone #: ###-#### Internet Inspection Request from: Joe Thomas ok to final 1/31/2005 4:40:58 PM
ELE04-02855 Final1/31/20051/31/20051/31/2005 12:00:00 AMPNH
bill; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles nh, called contr. and said to call when set-up. 1/31/2005 3:01:56 PM
ELE04-03481 Rough-In Permanent Service1/31/20051/31/20051/31/2005 12:00:00 AMPFAIL
verna; Phone #: ###-#### Internet Inspection Request from: Barbara Moore 110.3(B) all screws shall be installed in service disc for #8537, 300.4(A)(1) nailplate shall be installed in garage se corner #8535 for recpt ckt, and in upstairs master bedroom box shall be mounted. Called left message. 1/31/2005 12:37:07 PM
ELE05-00313 Final1/31/20051/31/20051/31/2005 12:00:00 AMPPASS
Ask for Tom Jones; Phone #: ###-#### Internet Inspection Request from: Richard Jones p/s o/h reconnect ok 1/31/2005 1:51:19 PM
ELE05-00256 Electrical Rough-In1/31/20051/31/20051/31/2005 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 1/31/2005 at 8:01:17 AM. Contact: ###-####. ok to cover walls only 1/31/2005 1:19:05 PM
ELE04-02817 Final1/31/20051/31/20051/31/2005 12:00:00 AMPPASS
###-#### - rex ok to final 1/31/2005 4:30:07 PM