Inspections for the day of: Tuesday, January 31, 2006.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00458 INSP-Supply line flush1/31/20061/31/20061/31/2006 6:37:57 PMPCANC
To be rescheduled per agreement with contractor per conversation.
FIR05-00458 INSP-Sprinkler Rough-in/Hydro1/31/20061/31/20061/31/2006 3:34:12 PMPPART
UG supply line hydrostatic test passed.
BLD02-00194 FIRE-Final Inspection1/31/20061/31/20061/31/2006 3:32:11 PMPPASS
Fire life safety is acceptable for the permitted scope of work.
FIR06-00002 INSP-Sprinkler Rough-in1/30/20061/31/20061/31/2006 1:24:35 PMAPART
Overhead rough-in at the grid ceiling areas are good for cover, noted that the north restroom has a water heater installed with a wooden platform for support above the restroom hard lid in a non-sprinkled space(protection required).
BLD05-02098 FIRE-Final Inspection1/31/20061/31/20061/31/2006 12:29:05 PMAPASS
The c/n item has been completed per D. Hannah, life safety finaled.
BLD06-00047 FIRE-Final Inspection1/30/20061/31/20061/31/2006 12:27:40 PMAFAIL
mike ###-#### Need to provide a fire ext. with current inspection tag mounted to the wall as discussed, the vanilla permit related fire sprinkler and alarm work must be finaled prior to life safety final for this TI.
BLD04-02203 FIRE-Final Inspection1/31/20061/31/20061/31/2006 12:23:17 PMPPASS
Fire life safety is acceptable for final, missing handle at fire ext. cabinet adjacent to south exterior exit door to be installed today per P. Doble. Noted that fire sprinkler heads in common fire areas are to be of the same response type at the divisions between remodel and exsisting areas, two missing escutcheons at restrooms to be re-installed today.
FIR05-00032 INSP-Final Inspection1/31/20061/31/20061/31/2006 11:56:44 AMPPASS
Fire sprinkler demo permitted work finaled.
FIR06-00042 INSP-Final Inspection1/30/20061/31/20061/31/2006 10:27:06 AMAFAIL
The cooking surface of one appliance exceeds 4' to the hood lip, nozzles at the smaller hood system failed to discharge during testing. Gas and power did shut down at both hoods during the test.
BLD05-02179 FIRE-Final Inspection1/26/20061/31/20061/27/2006 10:05:51 AMACANC
Phone #: ###-#### Internet Inspection Request from: Rob Puckett Inspection cancelled from web by: Rob Puckett