FIR05-00458
| INSP-Supply line flush | 1/31/2006 | 1/31/2006 | 1/31/2006 6:37:57 PM | P | CANC |
|
|
To be rescheduled per agreement with contractor per conversation.
|
FIR05-00458
| INSP-Sprinkler Rough-in/Hydro | 1/31/2006 | 1/31/2006 | 1/31/2006 3:34:12 PM | P | PART |
|
|
UG supply line hydrostatic test passed.
|
BLD02-00194
| FIRE-Final Inspection | 1/31/2006 | 1/31/2006 | 1/31/2006 3:32:11 PM | P | PASS |
|
|
Fire life safety is acceptable for the permitted scope of work.
|
FIR06-00002
| INSP-Sprinkler Rough-in | 1/30/2006 | 1/31/2006 | 1/31/2006 1:24:35 PM | A | PART |
|
|
Overhead rough-in at the grid ceiling areas are good for cover, noted that the north restroom has a water heater installed with a wooden platform for support above the restroom hard lid in a non-sprinkled space(protection required).
|
BLD05-02098
| FIRE-Final Inspection | 1/31/2006 | 1/31/2006 | 1/31/2006 12:29:05 PM | A | PASS |
|
|
The c/n item has been completed per D. Hannah, life safety finaled.
|
BLD06-00047
| FIRE-Final Inspection | 1/30/2006 | 1/31/2006 | 1/31/2006 12:27:40 PM | A | FAIL |
|
|
mike ###-#### Need to provide a fire ext. with current inspection tag mounted to the wall as discussed, the vanilla permit related fire sprinkler and alarm work must be finaled prior to life safety final for this TI.
|
BLD04-02203
| FIRE-Final Inspection | 1/31/2006 | 1/31/2006 | 1/31/2006 12:23:17 PM | P | PASS |
|
|
Fire life safety is acceptable for final, missing handle at fire ext. cabinet adjacent to south exterior exit door to be installed today per P. Doble. Noted that fire sprinkler heads in common fire areas are to be of the same response type at the divisions between remodel and exsisting areas, two missing escutcheons at restrooms to be re-installed today.
|
FIR05-00032
| INSP-Final Inspection | 1/31/2006 | 1/31/2006 | 1/31/2006 11:56:44 AM | P | PASS |
|
|
Fire sprinkler demo permitted work finaled.
|
FIR06-00042
| INSP-Final Inspection | 1/30/2006 | 1/31/2006 | 1/31/2006 10:27:06 AM | A | FAIL |
|
|
The cooking surface of one appliance exceeds 4' to the hood lip, nozzles at the smaller hood system failed to discharge during testing. Gas and power did shut down at both hoods during the test.
|
BLD05-02179
| FIRE-Final Inspection | 1/26/2006 | 1/31/2006 | 1/27/2006 10:05:51 AM | A | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Rob Puckett Inspection cancelled from web by: Rob Puckett
|