FIR06-00821
| FIR-Aging Inspection | 1/31/2007 | 1/31/2007 | 2/6/2007 3:19:55 PM | | NR |
|
|
work is in progress
|
BLD06-01946
| FIRE-Final Inspection | 1/31/2007 | 1/31/2007 | 1/31/2007 4:28:50 PM | P | PASS |
|
|
life safety finaled
|
BLD05-01009
| FIRE-Final Inspection | 1/31/2007 | 1/31/2007 | 1/31/2007 3:50:08 PM | P | PASS |
|
|
life safety finaled
|
FIR06-00938
| INSP-Final Inspection | 1/31/2007 | 1/31/2007 | 1/31/2007 3:04:43 PM | P | PASS |
|
|
Permit finaled
|
FIR06-00640
| INSP-Final Inspection | 1/30/2007 | 1/31/2007 | 1/31/2007 2:58:28 PM | A | FAIL |
|
|
The outside alarm bell did not operate with the flow switch. The lintel for the master shower was not deep enough but the contractor added depth to it as I waited.
|
MIS06-00223
| FIR-Final | 1/31/2007 | 1/31/2007 | 1/31/2007 2:56:41 PM | P | PASS |
|
|
Life safety finaled
|
BLD06-00271
| FIRE-Final Inspection | 1/30/2007 | 1/31/2007 | 1/31/2007 2:44:41 PM | P | FAIL |
|
|
Need to update the permit application since it says that the building will be sprinklered and it isn't. Also need to remove the thumbturn deadbolts and tag the fire extinguishers.
|
BLD06-02999
| FIRE-Final Inspection | 1/31/2007 | 1/31/2007 | 1/31/2007 1:38:45 PM | P | PASS |
|
|
life safety finaled
|
FIR06-00921
| INSP-Final Inspection | 1/30/2007 | 1/31/2007 | 1/31/2007 1:37:45 PM | P | PASS |
|
|
permit finaled. forward flush passed and the heads have been added at the columns located within the racking.
|
MIS07-00015
| FIR-Final | 1/31/2007 | 1/31/2007 | 1/31/2007 1:33:05 PM | P | PASS |
|
|
life safety finaled
|
FIR06-00905
| INSP-Final Inspection | 1/30/2007 | 1/31/2007 | 1/31/2007 12:42:27 PM | P | PASS |
|
|
permit finaled
|
FIR06-01003
| INSP-Final Inspection | 1/30/2007 | 1/31/2007 | 1/31/2007 10:49:54 AM | A | PASS |
|
|
permit finaled. Someone in the dollar store apparently silenced the alarm while we were testing. I told the property manager and the fire alarm contractor that the keys that allow an person to do this are to be removed from the annunciators.
|
FIR06-00600
| INSP-Sprinkler Rough-in/Hydro | 1/30/2007 | 1/31/2007 | 1/31/2007 10:28:38 AM | A | PASS |
|
|
Rough-in inspection passed except the backflow preventor is 6" instead of 4". New hydraulic calculations will be required. Overhead hydro test passed.
|
FIR05-00644
| INSP-Sprinkler Rough-in/Hydro | 1/30/2007 | 1/31/2007 | 1/31/2007 9:48:55 AM | A | PASS |
|
|
24 hour air tests for both the dry systems has passed.
|
FIR06-00977
| INSP-Sprinkler Rough-in/Hydro | 1/30/2007 | 1/31/2007 | 1/31/2007 8:49:46 AM | A | PART |
|
|
24 hour air test started at 8:45 with 41 psi on the guage
|