Inspections for the day of: Thursday, January 31, 2008.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-01005 INSP-Final Inspection1/31/20081/31/20081/31/2008 5:56:51 PMPPASS
Permit work is complete, c/n item has been done, fire sprinkler permit finaled.
FIR07-00450 INSP-Final Inspection1/29/20081/31/20081/31/2008 5:55:41 PMPPART
Bill please make after 1 pm Phone #: ###-#### Verified all noted correction items from the previous inspection dated 1/10 have been finished. Elevator recall, shunt trip, fire doors are all that remain to be tested prior to permit final (all three elevators).
BLD07-02928 FIRE-Final Inspection1/30/20081/31/20081/31/2008 5:50:19 PMPPASS
Fire life safety finaled.
FIR07-00947 INSP-Final Inspection1/30/20081/31/20081/31/2008 5:49:22 PMPPASS
Fire alarm final testing passed, corrections are complete, as-built plans provided.
BLD07-02755 FIRE-Final Inspection1/30/20081/31/20081/31/2008 2:10:59 PMPPASS
Correction notice items are finished, fire life safety passed.
BLD07-03046 FIRE-Final Inspection1/30/20081/31/20081/31/2008 1:55:57 PMAPASS
Fire life safety inspection passed.
BLD07-02967 FIRE-Final Inspection1/30/20081/31/20081/31/2008 12:36:51 PMAPART
Fire life safety is acceptable for the NW portion of the remodel area-"tax area" only at this time.
FIR07-00880 FIR-Aging Inspection1/31/20081/31/20081/31/2008 11:44:53 AM DEFR
Site work in progress, pending field inspection request.
FIR06-00365 INSP-Final Inspection1/30/20081/31/20081/31/2008 11:43:15 AMAPART
Preliminary walkthrough of the 1st and 5th floor units only, noted painted heads at some locations will not be accepted-heads cannot be cleaned but must be replaced due to paint at the seat or element-see units 102 and 505 for typical examples, also noted final head locations cannot be approved at this time due to missing lights and fixtures not yet installed for verification of proper clearances from obstructions.
FIR07-00846 INSP-Final Inspection1/30/20081/31/20081/31/2008 11:36:22 AMANR
Not ready for final per contractor, inspection rescheduled as discussed.
FIR07-00953 INSP-Final Inspection1/30/20081/31/20081/31/2008 11:35:05 AMAPASS
Fire alarm permit finaled.
BLD06-03584 FIRE-Final Inspection1/31/20081/31/20081/31/2008 7:01:20 AMACANC
Phone #: ###-#### Internet Inspection Request from: Greg Kirkes Inspection cancelled from web by: Greg Kirkes