Inspections for the day of: Tuesday, January 31, 2012.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00563 INSP-Sprinkler Rough-in/Hydro1/30/20121/31/20122/1/2012 8:00:40 AMPCANC
Inspection was performed during the morning requested time slot.
BLD12-00087 FIRE-Final Inspection1/31/20121/31/20121/31/2012 2:50:08 PMPPASS
life safety passed
BLD11-01512 FIRE-Final Inspection1/30/20121/31/20121/31/2012 2:45:20 PMPPART
A temporary occupancy is being given with Romeo Gervais permission until the kitchen area is complete. Per Sam, in plan review, the single action "paddle" hardware on the store front door from the Dining area is permissable.
FIR11-00612 INSP-Sprinkler Rough-in1/30/20121/31/20121/31/2012 2:20:08 PMPPASS
The sprinkler system rough-in passed for the Golf Galaxy and Home Fabrics canopies.
BLD12-00013 FIRE-Final Inspection1/27/20121/31/20121/31/2012 11:33:48 AMAPASS
life safety passed. The fire extinguisher is on its way from Don.
FIR12-00018 INSP-Final Inspection1/30/20121/31/20121/31/2012 11:08:32 AMAPASS
Permit finaled
BLD11-00565 FIRE-Final Inspection1/30/20121/31/20121/31/2012 11:00:11 AMAPASS
life safety passed
BLD12-00058 FIRE-Final Inspection1/25/20121/31/20121/31/2012 10:59:37 AMAFAIL
Repair the exit signs, provide emergency lighting in the Display area, remove hardware from the northwest store front door, provide racking permit for the storage racks that exceed 8' (racks are 12'), provide high pile storage permit, it appears that pendant sprinklers are overspaced in two locations in the Display area (product is 15' piled, 19' on the racks).
BLD12-00122 FIRE-Final Inspection1/30/20121/31/20121/31/2012 10:55:45 AMAPART
A temporary was given until the front and rear door hardware is corrected and the address is moved to the front of the building.
FIR12-00018 INSP-Sprinkler Rough-in/Hydro1/30/20121/31/20121/31/2012 9:30:29 AMAPASS
The sprinkler piping rough-in and hydro test passed.
FIR11-00563 INSP-Sprinkler Rough-in/Hydro1/30/20121/31/20121/31/2012 9:02:11 AMAPASS
The second floor west end piping can be covered. See the city approved plans for locations marked in red. I noted that insulation/tenting over the fourth floor corridor piping has been removed in several locations.
FIR09-00680 INSP-Final Inspection1/30/20121/31/20121/31/2012 9:00:36 AMAPASS
Permit finaled