Inspections for the day of: Tuesday, January 31, 2017.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJames Ady
TitleELE-INSPECTOR
Phone #914-4683
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-00171 Final1/30/20171/31/20171/31/2017 2:52:46 PMPPASS
final for LED retrofit- Contact Nick @ ###-#### Phone #: ###-#### Inspection requested via web by Steve Blackmer final ok
ELE16-02586 Final1/31/20171/31/20171/31/2017 2:37:08 PMPFAIL
Eric Phone #: ###-#### mainbath GFCI,Back patio W/P, Garage recep Kitchen island not tamper, Remove romex from A/C flex. Lock outs on DIsh, and Water heater. Garage receps non gfi protected. E Side garage receps revers polarity. Furnace disc cover plate. Garage door opener cover plate. Counter between living and kitchen GFCI protected.
ELE16-03325 Final1/31/20171/31/20171/31/2017 1:42:28 PMPFAIL
Code 2010 Phone #: ###-#### Inspection requested via web by Jason Wicks 210.52.C 1 Recep shall be installed within 24in of cook top 230.70. Each structure shall have disc. mean ( Detached garage) 314.20 Boxes set back more than1/4in shall have extension rings. (all weather proof, mirrors and Up stair 2gang for wall sconce.) 422.30 Furnace shall have Disc means. 334.12 B4 NM cable shall not be installed in wet location 300.9 the inside of an above ground conduit shall be considered a wet location (NM cable going to A/C disconnect)
ELE16-04054 Electrical Rough-In1/30/20171/31/20171/31/2017 9:49:21 AMAPASS
Contact is Rene Ramakers. This is a cover inspection. Phone #: ###-#### Inspection requested via web by Scott Campbell E side Duct bank OK to cover
ELE16-00770 Final1/30/20171/31/20171/31/2017 8:51:34 AMAPART
Final for temp C of O.
Only thing not completed is the HVAC contractor has not set AC units. Phone #: ###-#### Inspection requested via web by Tracy Robertson No A/C's set or Pool perimeter landscape receps. Pool on seperate permit. Fitness center only temp final ok