ELE18-01929
| Final | 1/31/2019 | 1/31/2019 | 1/31/2019 2:16:48 PM | P | NH |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk All areas locked. Unit 4 looks lived in. Reschedule when accessible.
|
ELE19-00391
| Permanent Service | 1/30/2019 | 1/31/2019 | 1/31/2019 1:56:43 PM | P | PASS |
|
|
There is a lock box on the back door if you need to get access with a code of 6737. Phone #: ###-#### Inspection requested via web by Jason Scott For final equipment grounding conductor to sub-panel shall be of sufficient size as per 250.122 #8 copper, #10 installed. p/s o/h rec ok
|
ELE18-04314
| Final | 1/31/2019 | 1/31/2019 | 1/31/2019 1:16:40 PM | P | FAIL |
|
|
Von. Phone #: ###-#### Inspection requested via web by Sean DeLacy 110.22- Each disconnecting means shall be identified as to its purpose. Secure panel cover right next to new service.
|
ELE18-04779
| Rough-In Permanent Service | 1/30/2019 | 1/31/2019 | 1/31/2019 11:38:10 AM | A | PASS |
|
|
New construction it''s open Phone #: ###-#### Inspection requested via web by Clayton Morgan Rough in ok cover p/s u/g n ok
|
ELE19-00371
| Electrical Rough-In | 1/30/2019 | 1/31/2019 | 1/31/2019 10:59:54 AM | A | PASS |
|
|
Underground cover Phone #: ###-#### Inspection requested via web by Shane Lott Southside aprox 30' from in ground box towards Rossi underground rough in ok cover
|
ELE18-00763
| Final | 1/30/2019 | 1/31/2019 | 1/31/2019 10:39:54 AM | A | FAIL |
|
|
Please call for access Phone #: ###-#### Inspection requested via web by John VanZandt 210.8(A)(1)- All receptacles installed to serve bathroom basins shall have GFCI protection. All basement bathroom receptacles. 210.8(A)(2)- All 15 and 20 amp 120 volt receptacle outlets installed in a garage shall have GFCI protection. Receptacle located on warm wall. 210.52(C)- In kitchens, pantries, and similar areas receptacle outlets installed to serve counter top surfaces shall be installed so no point measured along wall line is more than 24" from a receptacle. 250.122- Minimum equipment grounding conductor for a 30 amp circuit shall not be smaller than #10. #12 installed in AC whip.
|
ELE19-00341
| Permanent Service | 1/30/2019 | 1/31/2019 | 1/31/2019 9:25:31 AM | A | PASS |
|
|
Service Inspection Phone #: ###-#### Inspection requested via web by Kevin Perez p/s o/h rec ok
|
ELE19-00340
| Temporary Service | 1/30/2019 | 1/31/2019 | 1/31/2019 8:54:10 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
|