ELE01-00035
| Electrical Rough-In | 1/3/2001 | 1/4/2001 | 1/4/2001 12:00:00 AM | A | PASS |
|
|
###-####. garage/addition ele r/i. ok 1/4/2001 11:30:56 AM
|
ELE00-03647
| Final | 1/3/2001 | 1/4/2001 | 1/4/2001 12:00:00 AM | A | PASS |
|
|
JIM 863- 6373. shell & core, completed. 1/4/2001 11:31:38 AM
|
ELE01-00010
| Final | 1/3/2001 | 1/4/2001 | 1/4/2001 12:00:00 AM | A | CANC |
|
|
FN-RE-INSP -JEFF-- ###-#### . was inspected on: 01/03/01. 1/4/2001 7:41:36 AM
|
ELE01-00029
| Electrical Rough-In | 1/3/2001 | 1/4/2001 | 1/4/2001 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 01/03/2001 at 17:28:25. Contact: ###-####. phase #1; walls ele r/i. ok. 1/4/2001 11:29:53 AM
|
ELE00-04484
| Final | 1/3/2001 | 1/4/2001 | 1/4/2001 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 01/03/2001 at 17:29:54. Contact: ###-####. nec: 347-14. bends in EMT conduit shall not exceed 360 degrees. exterior wall packs at rear of building. 1/4/2001 4:47:40 PM
|
ELE00-03533
| Final | 1/4/2001 | 1/4/2001 | 1/4/2001 12:00:00 AM | P | PASS |
|
|
FN INSP-###-#### DON. corrections completed. ok. 1/4/2001 4:51:10 PM
|
ELE00-01032
| Final | 1/4/2001 | 1/4/2001 | 1/4/2001 12:00:00 AM | P | FAIL |
|
|
FN FOR GENERATOR- JERRY ###-####. requested fax of copy for field evaluation of test for emergency generator listing. 1/4/2001 4:50:30 PM
|
ELE01-00010
| Final | 1/4/2001 | 1/4/2001 | 1/4/2001 12:00:00 AM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 01/04/2001 at 09:26:14. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on 01/04/2001 at 10:52:52.
|