ELE04-02698
| ELE-Aging Inspection | 1/4/2006 | 1/4/2006 | 1/5/2006 8:12:12 AM | | DONE |
|
|
see final
|
ELE06-00022
| Final | 1/3/2006 | 1/4/2006 | 1/4/2006 4:40:54 PM | P | PASS |
|
|
north building of cloverdale funeral home///We installed a new 30 amp 120/230 volt circuit from the existing indoor panelboard inside the north building, overhead to a new outdoor panel with GFCI receptacles below it on the pole inside the Reindeer pen. Thanks!!!! Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ok to final
|
ELE05-03591
| Final | 1/4/2006 | 1/4/2006 | 1/4/2006 3:59:46 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 1/4/2006 at 8:05:29 AM. Contact: ###-####.corr made, ok to final, signed occ card
|
ELE06-00029
| Final | 1/4/2006 | 1/4/2006 | 1/4/2006 1:19:25 PM | P | CANC |
|
|
TEMPORARY POWER POLE; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy called contr, told no job id sticker, no address, could not be sure if at right pole, told that pole set has no gec abrasion protection broken 50a recpt, not use wire for u/g
|
ELE04-00301
| ELE-Aging Inspection | 1/4/2006 | 1/4/2006 | 1/4/2006 10:35:47 AM | | NR |
|
|
called contr to call in for final
|
ELE05-04120
| Final | 1/4/2006 | 1/4/2006 | 1/4/2006 10:34:35 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack ok to final
|
ELE05-01506
| ELE-Aging Inspection | 1/4/2006 | 1/4/2006 | 1/4/2006 10:23:55 AM | | DONE |
|
|
see final
|
ELE06-00019
| Electrical Rough-In | 1/3/2006 | 1/4/2006 | 1/4/2006 10:22:31 AM | A | CANC |
|
|
###-#### - nancy see conf
|
ELE05-04577
| Final | 1/3/2006 | 1/4/2006 | 1/4/2006 9:37:14 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 1/3/2006 at 12:46:42 PM. Contact: ###-####. called contr, left corr notice,250.53(G) electrode shall be flush with or below ground, at least 8' shall be in contact with soil
|
ELE05-04569
| Electrical Rough-In | 1/3/2006 | 1/4/2006 | 1/4/2006 9:22:11 AM | A | FAIL |
|
|
ANGELA; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, left corr notice, 300.4(D) mc cable shall be 1 1/4" from edge of framing member, 330.30(B) mc cable shall be secured within 12" of box, 314.4 metal box shall be grounded, 314.23 (B)(1) nails and screws used as fastening means shall be attached using brackets or within 1/4" of back or ends of enclosure,314.23(C) enclosure shall be rigidly secured
|
ELE05-01630
| Final | 1/3/2006 | 1/4/2006 | 1/4/2006 8:36:05 AM | A | PART |
|
|
General contractor is requesting temporary occupancy; Phone #: ###-#### Internet Inspection Request from: Nikki Day new construction area only ok to final, signed struct card, will do occ when job done
|
ELE06-00019
| Conference | 1/4/2006 | 1/4/2006 | 1/4/2006 12:00:00 AM | A | DONE |
|
|
told owner service shall be 8' over roof,add water ground to new service, make subpanel 4 wire
|
ELE05-01506
| Final | 1/4/2006 | 1/4/2006 | 1/4/2006 12:00:00 AM | A | PASS |
|
|
ok to final
|
ELE06-00019
| Final | 1/3/2006 | 1/4/2006 | 1/3/2005 12:00:00 AM | A | CANC |
|
|
###-#### - nancy - needs to be ri first
|