FIR05-00604
| FIR-Aging Inspection | 1/4/2006 | 1/4/2006 | 1/6/2006 1:47:44 PM | | NR |
|
|
Job status to be found out.
|
BLD05-02689
| FIRE-Final Inspection | 1/4/2006 | 1/4/2006 | 1/4/2006 4:44:06 PM | P | FAIL |
|
|
Provide fire extinguisher per review comments #2, final fire alarm permit.
|
FIR05-00312
| INSP-Supply line flush | 1/4/2006 | 1/4/2006 | 1/4/2006 4:27:50 PM | P | FAIL |
|
|
united water did not show up
|
FIR05-00447
| INSP-Sprinkler Rough-in/Hydro | 1/3/2006 | 1/4/2006 | 1/4/2006 3:14:50 PM | A | PASS |
|
|
wet and dry system hydro tests passed
|
BLD03-01575
| FIRE-Final Inspection | 1/4/2006 | 1/4/2006 | 1/4/2006 3:12:35 PM | P | CANC |
|
|
Duplicate inspection
|
BLD03-01575
| FIRE-Final Inspection | 1/4/2006 | 1/4/2006 | 1/4/2006 3:11:51 PM | P | FAIL |
|
|
odie; Phone #: ###-#### Remove thumbturn locks from all doors including the main exit. Provide sticker and indicator at the main exit. Sprinkler heads are overspaced on the Radiant Research side of the building in the sleep study area, outside the sleep study area on the north side and one pendant in the open office is too close to a column. Provide additional emergency lights as marked on the plans and repair the two emergency lights on the Selah side. Provide emergency lighting in the main lobby.
|
FIR05-00825
| INSP-Final Inspection | 1/3/2006 | 1/4/2006 | 1/4/2006 11:19:21 AM | A | FAIL |
|
|
zone 2 and 3 descriptions are not correct. need resubmitted plans
|
FIR05-00476
| INSP-Final Inspection | 1/3/2006 | 1/4/2006 | 1/4/2006 11:18:43 AM | A | FAIL |
|
|
zone 2 and 3 descriptions are not correct. need resubmitted plans
|
BLD05-01431
| FIRE-Final Inspection | 1/3/2006 | 1/4/2006 | 1/4/2006 10:36:26 AM | A | PASS |
|
|
Fire life safety finaled
|
BLD05-02890
| FIRE-Conference | 1/3/2006 | 1/4/2006 | 1/4/2006 12:00:00 AM | A | CANC |
|
|
randy; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ///cancelled per Randy 1/3/06 LEG
|
BLD04-02997
| FIRE-Final Inspection | 1/3/2006 | 1/4/2006 | 1/3/2006 1:35:16 PM | A | PASS |
|
|
fire life safety finaled
|