Inspections for the day of: Thursday, January 4, 2007.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-00711 Electrical Rough-In1/3/20071/4/20071/4/2007 4:56:09 PMPPART
Scheduled by a contractor via Hello! on 1/3/2007 at 2:03:45 PM. Contact: ###-####. 4th floor anop
ELE07-00041 Permanent Service1/4/20071/4/20071/4/2007 4:14:51 PMPNR
cal ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called contr needs to address 250.52(A)(1) grd water system, or 104(A)(1) bond water system called
ELE07-00043 Rough-In Permanent Service1/4/20071/4/20071/4/2007 3:50:17 PMPFAIL
SHAWN ###-#### 300.4(A)(1)&(D) nail plates and 11/4" for high and low voltage cables, 314.43 no nails in plastic boxes, 314.17(C) sheath shall enter box not tape where cables sheath is cut short upstairs in laundry rm switch and basement exit door switch 210.52(B) remove vacuum outlet from S A B C in din. rm334.23 protect all cables 6ft of attic accesses garage and MB closet
ELE07-00020 Final1/3/20071/4/20071/4/2007 2:19:48 PMPPASS
Call homeowner before heading out ###-####. Please inspect between 1:00 and 3:00 pm. Work performed by Tom Wonacott. Phone #: ###-#### ok
ELE07-00046 Electrical Rough-In1/4/20071/4/20071/4/2007 1:51:41 PMPPART
L&K Electric - uffer ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok
ELE06-01186 Conference1/4/20071/4/20071/4/2007 1:42:48 PMPDONE
elisha; Phone #: ###-#### Internet Inspection Request from: Cathy ok
ELE06-04433 Electrical Rough-In1/3/20071/4/20071/4/2007 12:19:07 PMPPART
contact: Jason Martineau ###-####- ceiling inspection please rm 108 t/o and ceiling cover ok
ELE06-04727 Final1/3/20071/4/20071/4/2007 10:47:44 AMAPASS
ron ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok
ELE06-04303 Final1/3/20071/4/20071/4/2007 9:35:18 AMAPASS
alan - cover on the grid and final - suite 105; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ceiling ok final ok no card
ELE06-04304 Final1/3/20071/4/20071/4/2007 9:34:34 AMAPASS
alan - cover on the grid and final - suite 104; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ceiling ok final ok no card
ELE07-00026 Electrical Rough-In1/3/20071/4/20071/4/2007 9:02:49 AMAPART
sid ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith walls ok
ELE07-00018 Electrical Rough-In1/3/20071/4/20071/4/2007 8:12:09 AMAPART
Scheduled by a contractor via Hello! on 1/3/2007 at 1:17:16 PM. Contact: ###-####. u/g floor boxes