BLD06-02578
| FIRE-Final Inspection | 1/4/2007 | 1/4/2007 | 1/4/2007 4:42:42 PM | P | NR |
|
|
No access due to carpet installation in progress at the time of inspection.
|
BLD06-02569
| FIRE-Final Inspection | 1/4/2007 | 1/4/2007 | 1/4/2007 4:41:49 PM | P | NR |
|
|
No access due to carpet installation in progress.
|
FIR05-00695
| INSP-Alarm Testing | 1/4/2007 | 1/4/2007 | 1/4/2007 3:48:50 PM | P | PART |
|
|
Fire alarm testing completed for the 11th floor guest rooms and common corridors. Three HC accessible rooms have strobe notification devices which are not in synchronization. No testing performed for the elevator lobby, service room, nac panels, or floor control for sprinkler monitoring at this time.
|
FIR06-00717
| INSP-Sprinkler Rough-in/Hydro | 1/4/2007 | 1/4/2007 | 1/4/2007 3:44:30 PM | P | PART |
|
|
The remainder of OH sprinkler rough-in is okay to cover.
|
FIR06-00814
| INSP-Sprinkler Rough-in/Hydro | 1/4/2007 | 1/4/2007 | 1/4/2007 3:43:04 PM | P | PART |
|
|
OH rough-in is good for cover at the drop ceiling areas, final pending ceiling tile and escutcheons.
|
FIR06-00526
| INSP-Sprinkler Rough-in/Hydro | 1/4/2007 | 1/4/2007 | 1/4/2007 2:04:35 PM | P | PART |
|
|
OH hydrostatic test for the new 3" main and new branch lines completed okay.
|
FIR06-00655
| INSP-Final Inspection | 1/2/2007 | 1/4/2007 | 1/4/2007 2:02:45 PM | P | PASS |
|
|
Fire sprinkler work is satisfactory, inspection passed, permit finaled.
|
BLD06-02719
| FIRE-Final Inspection | 1/4/2007 | 1/4/2007 | 1/4/2007 12:00:01 PM | P | PASS |
|
|
Required corrections have been made, fire life safety inspection passed.
|