Inspections for the day of: Thursday, January 4, 2007.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00601 FIR-Aging Inspection1/4/20071/4/20071/8/2007 3:05:49 PM NR
work is still in progress
BLD06-00115 FIRE-Final Inspection1/3/20071/4/20071/4/2007 4:09:12 PMAFAIL
Doors do not latch and a letter is needed from the architect stating he will not require the smoke detectors in the vaulted ceilings as noted on the electrical prints.
BLD06-00116 FIRE-Final Inspection1/3/20071/4/20071/4/2007 4:08:34 PMAFAIL
Doors do not latch and a letter is needed from the architect stating he will not require the smoke detectors in the vaulted ceilings as noted on the electrical prints.
BLD06-00117 FIRE-Final Inspection1/3/20071/4/20071/4/2007 4:07:50 PMAFAIL
Doors do not latch and a letter is needed from the architect stating he will not require the smoke detectors in the vaulted ceilings as noted on the electrical prints.
BLD06-00118 FIRE-Final Inspection1/3/20071/4/20071/4/2007 4:06:53 PMAFAIL
Doors do not latch and a letter is needed from the architect stating he will not require the smoke detectors in the vaulted ceilings as noted on the electrical prints.
MIS07-00001 FIR-Final1/3/20071/4/20071/4/2007 10:20:12 AMAFAIL
I stopped after 10:00 as online comment requested but the doors are locked and three attempts at with the provided phone number got no answer. No inspection performed.
FIR06-00815 INSP-Final Inspection1/3/20071/4/20071/4/2007 10:08:10 AMAPASS
Sprinkler piping is ok to cover. System will need annual inspection prior to final.
MIS06-00327 FIR-Final1/3/20071/4/20071/4/2007 9:27:57 AMAPASS
Life safety finaled
FIR06-00968 INSP-Final Inspection1/3/20071/4/20071/3/2007 4:06:39 PMAFAIL
The two duct smoke detectors test ok but this tenant space requires the building notification system to be extended into this new tenant space. A correction notice has been placed at the project site and Charlie and Peter with SimplexGrinnell have been notified.