ELE07-03479
| Final | 1/4/2008 | 1/4/2008 | 1/4/2008 4:08:18 PM | P | PASS |
|
|
ok
|
ELE07-03192
| Final | 1/4/2008 | 1/4/2008 | 1/4/2008 4:08:01 PM | P | PASS |
|
|
mike - please call 1/2 hr prior to inspection Phone #: ###-#### ok
|
ELE08-00035
| Permanent Service | 1/4/2008 | 1/4/2008 | 1/4/2008 2:49:25 PM | P | PASS |
|
|
Roy; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt p/s u/g new ok meter
|
ELE08-00035
| Final | 1/4/2008 | 1/4/2008 | 1/4/2008 2:48:55 PM | P | PASS |
|
|
Roy; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok
|
ELE07-03495
| Final | 1/4/2008 | 1/4/2008 | 1/4/2008 1:21:04 PM | P | FAIL |
|
|
PLease call Ted with any questions at ###-#### Phone #: ###-#### Internet Inspection Request from: Daniel Gamboa corr called 210.52(A) needs outlet wall spac e liv rm stair wall, 408.8 panel schedule all messed up shall be specific purpose and use, and correct circuits marked wrong
|
ELE07-02894
| Final | 1/4/2008 | 1/4/2008 | 1/4/2008 12:16:19 PM | P | PASS |
|
|
dino Phone #: ###-#### ok
|
ELE07-01982
| Final | 1/4/2008 | 1/4/2008 | 1/4/2008 10:46:31 AM | A | PASS |
|
|
ok
|
ELE07-02043
| Final | 1/4/2008 | 1/4/2008 | 1/4/2008 10:29:25 AM | A | PASS |
|
|
|
ELE07-04213
| Final | 12/31/2007 | 1/4/2008 | 1/4/2008 9:44:33 AM | A | FAIL |
|
|
richard Phone #: ###-####corr. called T310.15(B)(2)(a) derate wires 2" pvc, 312.5 cables not allowed in 2" pvc,also provide connectors for cables in back of panel, 200.6&7 shall not ID 6 or smaller, red #12 used as neutral, re ID white in 10/2 for water heater, 250.53(D)(2) needs 2 grd rods, 230.24 make sure service drop and drip loop have required clearence note remove old #8 GEC from service panel and call for r/i p/s not final
|
ELE07-01982
| ELE-Aging Inspection | 1/4/2008 | 1/4/2008 | 1/4/2008 7:38:49 AM | | DONE |
|
|
|
ELE07-02043
| ELE-Aging Inspection | 1/4/2008 | 1/4/2008 | 1/4/2008 7:36:46 AM | | DONE |
|
|
|