ELE06-00820
| ELE-Aging Inspection | 1/4/2008 | 1/4/2008 | 1/11/2008 7:42:30 AM | | DONE |
|
|
contractor should still call when ready
|
ELE08-00028
| Rough-In Permanent Service | 1/3/2008 | 1/4/2008 | 1/4/2008 4:13:04 PM | P | CANC |
|
|
Blake ###-#### see ri
|
ELE08-00028
| Electrical Rough-In | 1/4/2008 | 1/4/2008 | 1/4/2008 3:13:04 PM | P | PASS |
|
|
Blake ###-#### ric walls only ok
|
ELE08-00029
| Rough-In Permanent Service | 1/3/2008 | 1/4/2008 | 1/4/2008 3:10:53 PM | P | CANC |
|
|
Blake ###-#### see ri
|
ELE08-00029
| Electrical Rough-In | 1/4/2008 | 1/4/2008 | 1/4/2008 2:37:00 PM | P | PASS |
|
|
Blake ###-#### u/g for recpt, and walls only ok to cover
|
ELE08-00034
| Electrical Rough-In | 1/4/2008 | 1/4/2008 | 1/4/2008 2:16:14 PM | P | FAIL |
|
|
jake - please call for access Phone #: ###-#### called contractor, left correction notice, nec 300.14 at least 6" free conductor shall be in boxes from where sheath enters box, 210.11(C) (3) bathrooms shall be supplied from 20a circuit with no other outlets, 210.12(B) bedrooms shall be protected by arc-fault circuit interrupters, 250.140 shall provide for range and dryer frame grounding per 250.134 and or 1138
|
ELE07-03837
| Final | 1/2/2008 | 1/4/2008 | 1/4/2008 1:25:23 PM | P | CANC |
|
|
bill Phone #: ###-#### see conference
|
ELE07-03837
| Conference | 1/4/2008 | 1/4/2008 | 1/4/2008 1:25:15 PM | P | DONE |
|
|
bill Phone #: ###-#### met contractor, talked about BCC no violations shall be retained, open up ceilings, no low voltage to be on grid, showroom receptacles, strapping conduit and raceways, etc
|
ELE07-03949
| Final | 1/3/2008 | 1/4/2008 | 1/4/2008 10:30:41 AM | A | PASS |
|
|
Any questions or concerns please call Clay at ###-####. Thanks. Phone #: ###-#### Internet Inspection Request from: Clay Morgan ok to final
|
ELE07-04202
| Final | 1/3/2008 | 1/4/2008 | 1/4/2008 9:44:47 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 1/3/2008 at 2:19:51 PM. Contact: ###-####. ok to final
|
ELE08-00002
| Electrical Rough-In | 1/3/2008 | 1/4/2008 | 1/4/2008 8:52:33 AM | A | PASS |
|
|
READY FOR FINAL OPEN ACCESS ALL DAY CALL BRIAN WITH QUESTIONS Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ric ok
|
ELE08-00002
| Final | 1/4/2008 | 1/4/2008 | 1/4/2008 8:52:21 AM | A | PASS |
|
|
READY FOR FINAL OPEN ACCESS ALL DAY CALL BRIAN WITH QUESTIONS Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ok to final
|
ELE08-00027
| Final | 1/3/2008 | 1/4/2008 | 1/4/2008 7:58:32 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Dan Rohl called contractor, ok to final
|
ELE08-00027
| Electrical Rough-In | 1/4/2008 | 1/4/2008 | 1/4/2008 7:57:58 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Dan Rohl ric ok, saw u/g on other permit
|