Inspections for the day of: Friday, January 4, 2008.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00818 INSP-Sprinkler Rough-in1/3/20081/4/20081/7/2008 8:12:27 AMPNR
Work is not ready for inspection per contractor.
BLD07-02112 FIRE-Supply Line Hydro1/4/20081/4/20081/4/2008 4:04:47 PMPCANC
Incorrect inspection type, was intended for the plumbing permit work.
FIR07-01004 INSP-Sprinkler Rough-in1/4/20081/4/20081/4/2008 3:16:21 PMPPART
Overhead fire sprinkler system modifications are acceptable.
FIR07-00989 INSP-Sprinkler Rough-in/Hydro1/3/20081/4/20081/4/2008 3:15:10 PMAPART
Noted areas okayed for cover, minor field modifications to be reflected on as-built drawings, need to perform a hydrostatic test on the new system mains and branch lines, underfloor mods approved, discussed project phasing.
FIR07-00191 INSP-Final Inspection1/3/20081/4/20081/4/2008 3:12:00 PMAPASS
Fire sprinkler permit finaled.
FIR07-00957 INSP-Sprinkler Rough-in/Hydro1/3/20081/4/20081/4/2008 1:11:06 PMAPART
OH hydrostatic testing passed, also inspected overhead rough-in and noted some issues including missing flex couplings at the riser, need bags at the heads in the paint and spray booths, provide retaining straps at the beam clamps, need to certify DCVA, noted 286 deg. heads have been installed in lieu of 200 deg. as indicated on plans, the two DSW heads at the exhaust ducts are not yet installed.
BLD07-00222 FIRE-Final Inspection1/4/20081/4/20081/4/2008 11:43:22 AMPPASS
C/N items are completed, life safety inspection passed.
FIR07-00677 FIR-Aging Inspection1/4/20081/4/20081/4/2008 11:37:17 AM DEFR
wip
FIR07-00973 INSP-Final Inspection1/2/20081/4/20081/4/2008 11:35:30 AMAFAIL
Need plan resubmittals reflecting actual field installation due to supply main relocation.
FIR07-00924 INSP-Sprinkler Rough-in1/2/20081/4/20081/4/2008 11:33:14 AMAPART
Overhead fire sprinkler system modifications are approved for cover at the drop ceilings.
BLD07-02501 FIRE-Final Inspection1/3/20081/4/20081/4/2008 10:22:34 AMAPASS
Fire life safety passed field inspection.