Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD09-00864 FIRE-Conference12/16/200912/29/2009 A 
Evelyn phone ###-#### Follow up on occupancy.
FIR09-00718 INSP-Final Inspection1/4/20101/4/20101/4/2010 4:07:34 PMPPASS
Permit finaled. The netcon rating was verified at 5 and all signals have been reverified.
FIR09-00703 INSP-Sprinkler Rough-in1/4/20101/4/20101/4/2010 3:57:33 PMPCANC
permit cancelled due to time constraints. Has been rescheduled for tomorrow morning
BLD09-01241 FIRE-Final Inspection1/4/20101/4/20101/4/2010 3:49:31 PMPFAIL
Emergency light needs repaired, and the two fire extinguishers need to be provided per the fire review comments.
BLD09-01786 FIRE-Final Inspection1/4/20101/4/20101/4/2010 3:48:30 PMPPASS
LIfe safety passed
FIR09-00575 INSP-Sprinkler Rough-in/Hydro12/31/20091/4/20101/4/2010 3:48:01 PMAPART
All sprinkler piping is ok to cover except the elevator lobby in the southeast corner of the second floor. In this location, I noted overspaced upright and pendant heads and the 1 1/4" branchline needs a hanger.