Inspections for the day of: Friday, January 4, 2013.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00663 INSP-Sprinkler Rough-in1/4/20131/4/20131/4/2013 3:45:44 PMPFAIL
This was a tenting inspection. The tenting is still not secured to the trusses in many locations and can be easily moved. Piping is not approved for cover.
FIR12-00758 INSP-Final Inspection1/4/20131/4/20131/4/2013 3:24:08 PMPPASS
Permit finaled
BLD12-01929 FIRE-Final Inspection1/3/20131/4/20131/4/2013 3:23:17 PMAPART
A temporary occupancy for the new construction area was given with scott arellano's permission until the project related fire alarm permit has been re-issued. Life safety items appeared ok.
FIR12-00505 INSP-Final Inspection1/3/20131/4/20131/4/2013 3:22:24 PMPPART
A temporary occupancy for the new construction area was given with scott arellano's permission until the project related fire alarm permit has been re-issued. It is at the fire inspectors discression to require EOL verification when the plans are re-issued.
BLD12-03310 FIRE-Final Inspection1/4/20131/4/20131/4/2013 3:15:03 PMPPASS
Life safety passed
FIR12-00199 INSP-Final Inspection1/3/20131/4/20131/4/2013 2:38:04 PMPCANC
These plans are to be resubmitted per Earl and will be rescheduled later.
FIR12-00604 INSP-Final Inspection1/3/20131/4/20131/4/2013 2:00:23 PMPFAIL
Need the spare heads/wrench for the head box and the backflow certified.
FIR12-00719 INSP-Final Inspection1/3/20131/4/20131/4/2013 1:58:31 PMPFAIL
Permit will be ok to final when a knox key box is provided. Will need NFPA 72 forms as well.
FIR12-00663 INSP-Sprinkler Rough-in/Hydro1/4/20131/4/20131/4/2013 12:08:45 PMPFAIL
Sprinkler rough-in for both floors passed but piping can not be covered on the second floor until the tenting has been repaired. Also the hydro test failed again.Starting presure was at 222psi and ended at 213psi.
BLD12-03217 FIRE-Final Inspection1/3/20131/4/20131/4/2013 11:34:22 AMAPASS
life safety passed
BLD06-02323 FIRE-Final Inspection1/3/20131/4/20131/4/2013 8:57:23 AMAPART
Blg 2 unit 203 life safety passed.
BLD12-03050 FIRE-Final Inspection1/3/20131/4/20131/4/2013 8:43:45 AMAPASS
Life safety passed. Per conversation with contractor the annual inspection for the fire extinguishers will be taken care of today.
FIR12-00726 INSP-Final Inspection1/3/20131/4/20131/4/2013 8:40:16 AMAPASS
Permit finaled