Inspections for the day of: Monday, January 4, 2016.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-00089 Final12/30/20151/4/20161/4/2016 2:02:40 PMPFAIL
Call prior to going Phone #: 3520355 >> Inspection requested via mobile web by Dan monzo 422.31 fixed appliances shall have a lockout(dishwasher)-406.9 receptacles installed outdoors shall be W/R type and have a listed in-use cover
ELE15-03725 Final1/4/20161/4/20161/4/2016 1:51:23 PMPPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn final ok
ELE15-02122 Final1/4/20161/4/20161/4/2016 12:45:55 PMPFAIL
Dennis Phone #: ###-#### 210.12 all receptacles in a bedroom including smoke detectors shall have AFCI protection(smoke and outlet on closet wall not protected)
ELE15-04121 Final12/30/20151/4/20161/4/2016 9:42:46 AMAPASS
If you have any questions, please call Jake ###-####. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan final ok
ELE15-04121 Electrical Rough-In12/30/20151/4/20161/4/2016 9:42:15 AMAPASS
If you have any questions, please call Jake ###-####. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan rough-in for ejector pump ok
ELE15-03097 Final1/2/20161/4/20161/4/2016 8:44:27 AMAPASS
Lock box 2265. Call me if you have questions. Thanks Clay ###-#### Phone #: ###-#### Inspection requested via web by Clay Morgan final ok