ELE12-02995
| ELE-Aging Inspection | 1/4/2017 | 1/4/2017 | 1/5/2017 3:12:32 PM | | CANC |
|
|
too busy
|
ELE16-03229
| Permanent Service | 12/29/2016 | 1/4/2017 | 1/4/2017 1:01:02 PM | P | CANC |
|
|
Jake is the contact his cell no. is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates...rescheduled to next day pm
|
ELE16-04166
| Electrical Rough-In | 12/30/2016 | 1/4/2017 | 1/4/2017 11:53:07 AM | P | CANC |
|
|
Call me with 15 minutes notice and I can meet you there for access. Thank You. Phone #: ###-#### Inspection requested via web by Craig Korell....
contractor agreed to cancel inspection...no hurry for inspection...roads and accessibility to rough...contract is only to finish service to new TI
|
ELE16-03370
| Final | 1/4/2017 | 1/4/2017 | 1/4/2017 11:48:12 AM | P | PASS |
|
|
Phone #: 2083425188 >> Inspection requested via mobile web by Chris Hopkins...
ok to final...labelling and disconnect means
|
ELE16-02883
| Final | 1/4/2017 | 1/4/2017 | 1/4/2017 10:49:03 AM | P | PASS |
|
|
Tyler Phone #: ###-####...
all corrections made...ok to final
|
ELE16-02883
| Electrical Rough-In | 1/3/2017 | 1/4/2017 | 1/4/2017 10:48:32 AM | A | PASS |
|
|
Tyler Phone #: ###-####...
ok to cover open sheetrock areas and replace outlets that were removed to verify right wire...oultet rewired to correct wire
|
ELE17-00009
| Electrical Rough-In | 1/3/2017 | 1/4/2017 | 1/4/2017 9:45:18 AM | A | FAIL |
|
|
Rough inspection for the dining room addition only at this time. Please call prior to inspection. Want to make sure you have access as the home is occupied. Phone #: ###-#### Inspection requested via web by Ryan Kohler...
1..junction box needs sized for number of wires..314.16
2..dining room outlets shall be on 20amp circuit on small appliance circuit..210.52(B)(1)
3...all wallspace 2ft or larger shall have an outlet..210.52(A)(2)
|
ELE16-03861
| Final | 1/3/2017 | 1/4/2017 | 1/4/2017 9:01:59 AM | A | PASS |
|
|
Jimmy Phone #: ###-####...
ok to final
|
ELE16-03382
| Final | 1/3/2017 | 1/4/2017 | 1/4/2017 8:39:53 AM | A | PASS |
|
|
The Homeowner will be home in the morning. Any questions please call Jake ###-####. Phone #: ###-#### Inspection requested via web by Clay Morgan....
ok to final....floor heat had no rough in inspection...homeowner had pictures of installation for me to view...gfi protection is working...electrical contractor takes responsibility of integrity of floor heat
|
ELE14-00519
| ELE-Request for Extension | 1/3/2017 | 1/4/2017 | 1/3/2017 12:45:09 PM | P | PASS |
|
|
Clark Phone #: ###-####..
still under construction...extension ok
|