Inspections for the day of: Wednesday, January 4, 2017.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00322 INSP-Final Inspection12/30/20161/4/20171/4/2017 12:22:51 PMPCANC
Could not test level 2 due to a cut pipe, cut to piping was made after hydrostatic test. Alarm inspection failed due to sync issues on level 4, cannot perform final inspection on fire sprinklers until fire alarm issue is resolved.
FIR16-00437 INSP-Final Inspection1/3/20171/4/20171/4/2017 12:18:51 PMPFAIL
Audible devices on level 4 are going out of sync, alarms will need to be re-inspected.
FIR16-00510 INSP-Sprinkler Rough-in/Hydro12/30/20161/4/20171/4/2017 11:17:51 AMPPART
Rough to cover ispection for overhead fire sprinkler piping on levels 1 and 2 complete, approved for cover, hydrostatic test will be completed at a later date.
FIR16-00223 INSP-Sprinkler Rough-in1/3/20171/4/20171/4/2017 10:52:03 AMADONE
Request was for a conference, discussed options for structural beams located on level 2.
FIR16-00656 INSP-Final Inspection1/4/20171/4/20171/4/2017 10:30:43 AMPCANC
Inspection request rescheduled due to scheduling conflict.
FIR16-00535 INSP-Final Inspection1/3/20171/4/20171/4/2017 10:30:22 AMPCANC
Inspection request rescheduled due to scheduling conflict.
FIR16-00594 INSP-Final Inspection1/4/20171/4/20171/4/2017 10:07:48 AMPPART
Partial final inspection complete for fire alarm system, city approved drawings match the installation. Need to verify audio shutdown on DJ equipment during a fire alarm event, permit cannot be finaled until audio shutdown is inspected and passed.