Inspections for the day of: Monday, January 5, 2004.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE03-03127 ELE-Aging Inspection1/5/20041/5/20041/5/2004 12:00:00 AM PASS
ELE03-03053 Permanent Service12/30/20031/5/20041/5/2004 12:00:00 AMAPASS
Benchmark's job at Brico site; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH
p/s u/g new ok 1/5/2004 8:41:36 AM
ELE03-03944 Final1/2/20041/5/20041/5/2004 12:00:00 AMAFAIL
###-#### rob loose recepts, needs approved lock out clip for breakers, handycap apart not ready open grd recepts, met contractor 1/5/2004 9:44:29 AM
ELE03-02975 Final1/2/20041/5/20041/5/2004 12:00:00 AMAFAIL
###-#### rob see PM# 3944 for info 1/5/2004 9:45:08 AM
ELE03-02458 Final1/5/20041/5/20041/5/2004 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 1/5/2004 at 7:11:52 AM. Contact: ###-####. not ready and cor. posted 210.8(B) gfci for all outlets in bathrm area, 620.52 warning signs for elevator disconnects, 400.8 shall not use cord as fixed wiring 1/5/2004 3:37:14 PM
ELE03-02975 Final1/5/20041/5/20041/5/2004 12:00:00 AMPCANC
Scheduled by a contractor via Hello! on 1/5/2004 at 7:32:37 AM. Contact: ###-####.
ELE03-03944 Final1/5/20041/5/20041/5/2004 12:00:00 AMPCANC
Scheduled by a contractor via Hello! on 1/5/2004 at 7:34:06 AM. Contact: ###-####.
ELE03-03634 Final1/5/20041/5/20041/5/2004 12:00:00 AMPCANC
chuck ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie see added r/i
1/5/2004 12:32:33 PM
ELE03-03871 Electrical Rough-In1/5/20041/5/20041/5/2004 12:00:00 AMPFAIL
ray; Phone #: ###-#### Internet Inspection Request from: Annette Moore cor. posted called 314.16, 250.148 splice all equip grds at boxes, 210.52(A)&(B) outlet wall, and countertop spacing, 300.14 wires way too short grds at boxes, 404.8 breakers higher than 6ft 7inches 1/5/2004 3:34:58 PM
ELE03-03634 Electrical Rough-In1/5/20041/5/20041/5/2004 12:00:00 AMPPASS
r/i ok