ELE04-03963
| Electrical Rough-In | 1/4/2005 | 1/5/2005 | 1/5/2005 12:00:00 AM | A | PASS |
|
|
CONATCT: JOHN OSTALOSA; Phone #: ###-#### Internet Inspection Request from: Deb McCoy ok 1/5/2005 9:27:58 AM
|
ELE04-04042
| Electrical Rough-In | 1/4/2005 | 1/5/2005 | 1/5/2005 12:00:00 AM | A | PART |
|
|
Jason; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie r/i ok fire job 1/5/2005 8:48:12 AM
|
ELE05-00032
| Final | 1/4/2005 | 1/5/2005 | 1/5/2005 12:00:00 AM | A | PART |
|
|
Tub located in beside house behind gate, connected from existing disconnect to tub. Internet Inspection Request from: Andy Rose tub ok needs contractor to check on required gfci outlet between 10ft and 20ft could not check no access to inside house 1/5/2005 12:08:40 PM
|
ELE05-00036
| Electrical Rough-In | 1/4/2005 | 1/5/2005 | 1/5/2005 12:00:00 AM | A | PASS |
|
|
###-####- pat ok 1/5/2005 12:06:53 PM
|
ELE04-02571
| Conference | 1/4/2005 | 1/5/2005 | 1/5/2005 12:00:00 AM | A | DONE |
|
|
Conference with Jim Smear. Call Matt White-electrician before going out to gain access. ; Phone #: ###-#### Internet Inspection Request from: Dana Moyer electrician still has not made correction , he does not think he needs a listed pool light jbox 1/5/2005 8:12:07 AM
|
ELE04-04059
| Electrical Rough-In | 1/4/2005 | 1/5/2005 | 1/5/2005 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 1/4/2005 at 6:23:07 PM. Contact: ###-####. r/i ok 1/5/2005 10:08:46 AM
|
ELE04-03963
| Final | 1/5/2005 | 1/5/2005 | 1/5/2005 12:00:00 AM | A | PASS |
|
|
ok card signed
|
ELE04-03678
| Electrical Rough-In | 1/5/2005 | 1/5/2005 | 1/5/2005 12:00:00 AM | P | PASS |
|
|
CONTACT: SHANE KORTE; Phone #: ###-#### Internet Inspection Request from: Deb McCoy ok 1/5/2005 3:29:58 PM
|
ELE05-00041
| Electrical Rough-In | 1/5/2005 | 1/5/2005 | 1/5/2005 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 1/5/2005 at 10:56:21 AM. Contact: ###-####. cor. posted called 250.148 shall grd metal boxes at time of r/i inspection 1/5/2005 1:21:40 PM
|
ELE05-00036
| Permanent Service | 1/5/2005 | 1/5/2005 | 1/5/2005 12:00:00 AM | P | PASS |
|
|
p/s o/h rec. ok
|
ELE04-01954
| Electrical Rough-In | 1/5/2005 | 1/5/2005 | 1/5/2005 12:00:00 AM | P | PART |
|
|
electrode ok for concrete cover
|
ELE04-02636
| Final | 1/5/2005 | 1/5/2005 | 1/5/2005 12:00:00 AM | P | FAIL |
|
|
cor. and reinspection fee due posted 314.16 box fill 110.3(A) replace damaged boxes, call for r/i of added boxes and request inspection for the correct address , called for kit area
|
ELE04-03342
| Final | 1/5/2005 | 1/5/2005 | 1/5/2005 12:00:00 AM | P | FAIL |
|
|
verna; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called wrong address again inspection is for 8479-81 evening star pm#ele04-02636 see added inspection for correct address 1/5/2005 1:45:21 PM
|
ELE04-01954
| Permanent Service | 1/5/2005 | 1/5/2005 | 1/5/2005 12:00:00 AM | P | NR |
|
|
Scheduled by a contractor via Hello! on 1/5/2005 at 8:23:04 AM. Contact: ###-####. see added r/i for concrete encased electrode 1/5/2005 1:20:01 PM
|
ELE04-02571
| Conference | 1/4/2005 | 1/5/2005 | 1/4/2005 4:06:43 PM | A | CANC |
|
|
Jim Smear for conference.; Phone #: ###-#### Internet Inspection Request from: Dana Moyer Inspection cancelled from web by: Dana Moyer
|