Inspections for the day of: Wednesday, January 5, 2005.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00057 INSP-Final Inspection12/30/20041/5/20051/5/2005 12:00:00 AMAFAIL
The toaster under the fryer hood did not lose power when the suppression system activated. All other items worked. Pull station locations are ok to remain as is. 1/5/2005 10:19:47 AM
FIR04-00623 INSP-Sprinkler Rough-in1/4/20051/5/20051/5/2005 12:00:00 AMAFAIL
Provide trip test and hydro test for the overhead system per review notes #60 and #61. Provide flexible coupling at the tie in per plans and review notes. 1/5/2005 12:41:55 PM
FIR04-00778 INSP-Sprinkler Rough-in1/5/20051/5/20051/5/2005 12:00:00 AMPCANC
Duplicate inspection 1/5/2005 2:54:35 PM
FIR04-00778 INSP-Final Inspection1/5/20051/5/20051/5/2005 12:00:00 AMPFAIL
Provide access to the east side of the new wall for inspection of the existing sprinkler heads. Provide annual inspection for the existing sprinkler riser. I notified manager of Emser Tile that the new area is not to be used until all inspections had been approved or action would be taken by the building and fire departments. 1/5/2005 2:56:27 PM
FIR04-00627 INSP-Sprinkler Rough-in1/5/20051/5/20051/5/2005 12:00:00 AMPPART
The remaining underground supply piping to the tie in at the street is ok to cover. The underground supply piping from the roadway the the stub out still needs inspection 1/5/2005 2:54:04 PM
FIR04-00689 INSP-Final Inspection1/5/20051/5/20051/5/2005 12:00:00 AMPFAIL
No approved plans on site. Contractor was gone 1/5/2005 4:23:35 PM